Table: Function selecting item code (DN)

(Items necessary to perform the applied control at the local site are described.)

DN

Item

 

 

Description

 

At shipment

 

 

 

 

 

 

 

 

01

Filter display delay

0000

: None

 

0001

: 150H

According to type

 

timer

0002

: 2500H

 

0003

: 5000H

 

 

 

 

0004

: 10000H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

Dirty state of filter

0000

: Standard

 

 

 

0000

: Standard

 

 

0001

: High degree of dirt (Half of standard time)

 

 

 

 

 

 

 

 

 

 

 

03

Central control

0001

: No.1 unit

to

0064

: No.64 unit

0099

: Unfixed

 

address

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

Specific indoor unit

0000

: No priority

 

0001

: Priority

0000

: No priority

 

priority

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

Heating temp shift

0000

: No shift

 

0001

: +1°C

0002

: +2°C

 

 

0002

: +2°C

to

0010

: +10°C

(Floor type 0000: 0°C)

 

 

 

 

 

 

(Up to +6 recommended)

 

 

 

 

 

 

 

 

 

 

 

0d

Existence of [AUTO]

0000

: Provided

 

 

 

0001

: Not provided

 

mode

0001

: Not provided (Automatic selection from connected outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

0E

Follows operation

0000

: Does not follow

 

 

 

0000

: Not provided

 

mode of the header

0001

: Follows

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0F

Cooling only

0000

: Heat pump

 

 

 

0000

: Heat pump

 

 

0001

: Cooling only (No display of [AUTO] [HEAT])

 

 

 

 

 

 

 

 

10

Type

0000

: (1-way air discharge cassette)

 

According to model type

 

 

0001

: (4-way air discharge cassette) to 0037

 

 

 

 

 

 

 

 

 

11

Indoor unit capacity

0000

: Unfixed

 

0001 to 0034

According to capacity type

 

 

 

 

 

 

 

 

 

12

Line address

0001

: No.1 unit

to

0030

: No.30 unit

0099

: Unfixed

 

 

 

 

 

 

 

 

 

13

Indoor unit address

0001

: No.1 unit

to

0064

: No.64 unit

0099

: Unfixed

 

 

 

 

 

 

 

 

14

Group address

0000

: Individual

 

0001 : Header unit of group

0099

: Unfixed

 

 

0002

: Follower unit of group

 

 

 

 

 

 

 

 

 

 

 

 

19

Louver type

0000

: Not provided

 

0001

: Swing only

According to type

 

(Adjustment of air

0004

: [4-way Air Discharge Cassette type] and [Under Ceiling type]

 

 

 

direction)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1E

Temp difference of

0000

: 0 deg

to

0010

: 10 deg

0003

: 3 deg

 

[AUTO] mode

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

 

(Ts±1.5)

 

selection COOL

 

 

 

 

 

 

 

 

HEAT, HEAT COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

Automatic restart of

0000

: None

 

0001

: Restart

0000

: None

 

power failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29

Operation condition

0000

: Usual

 

0001

: Condition ignored

0000

: Usual

 

of humidifier

(Detection control for heat exchanger temperature)

 

 

 

 

 

 

 

 

 

 

 

2A

Selection of option/

0000

: Filter input

 

0001

: Alarm input (Air washer, etc.)

0002

: None

 

error input (CN70)

0002

: None

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2E

HA terminal (CN61)

0000

: Usual

 

0001

: Leaving-ON prevention control

0000

: Usual

 

select

 

 

 

 

 

 

(HA terminal)

 

 

 

 

 

 

 

 

 

30

Automatic elevating

0000

: Unavailable

 

0001

: Available

0000

: Unavailable

 

grille

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

Ventilating fan

0000

: Unavailable

 

0001

: Available

0000

: Unavailable

 

control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

TA sensor selection

0000

: Body TA sensor

 

0001

: Remote controller sensor

0000

: Body TA sensor

 

 

 

 

 

 

 

 

33

Temperature unit

0000

: °C (at factory shipment)

 

 

0000

: °C

 

select

0001

: °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

Drain pump control

0000

: None

 

0001

: Pump ON

0003

: Pump OFF

 

 

0002

: None

 

0003

: Pump OFF

 

 

 

 

 

 

 

5d

High ceiling selection

[4-way Air Discharge Cassette type] and [Under Ceiling type]

0000

: Standard

 

(Air volume selection)

0000

: Standard filter

 

0001

: Super-long life filter

 

 

 

 

0003

: High efficiency filter

 

 

 

 

 

 

[Concealed Duct Standard type]

 

 

 

 

 

 

0000

: Standard static pressure (40Pa)

 

 

 

 

 

0001

: High static pressure 1 (70Pa)

 

 

 

 

 

0003

: High static pressure 2 (100Pa)

 

 

 

 

 

0005

: Correspond to quiet sound

 

 

 

 

 

 

0006

: Low static pressure (20Pa)

 

 

 

 

 

 

 

 

 

 

 

 

60

Timer set

0000

: Available (Operable)

 

 

0000

: Available

 

(Wired remote

0001

: Unavailable (Operation prohibited)

 

 

 

controller)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

Anti-ceiling

0000

: Clear

 

 

 

4- way Air Discharge

 

smudging control

 

 

 

 

 

Cassette type only

 

 

 

 

 

 

 

 

 

72

Page 72
Image 72
Toshiba MMU-AP0091H service manual Description At shipment, HEAT, Heat → Cool