150

Check code

Check code name

Cause of operation

[H16] / [d7]

TK2 detective circuit system error

 

1. Connection of TK2 sensor.

(TCC-L / AI-NET)

 

(Sub-code: 02)

 

2. Error in resistance value of TK2 sensor

 

 

 

 

 

(see 9-7 Sensor characteristics).

 

 

 

 

 

3. Oil-equalization circuit error

 

 

 

 

 

(check valve, capillary clogging,

 

 

 

 

 

strainer clogging).

 

 

 

 

 

4. Refrigerant stagnation in case of

 

 

 

 

 

compressor shell.

 

 

 

 

 

 

 

 

 

Has TK2 sensor become detached?

YES

 

 

 

Correct installation of sensor.

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct wiring/installation.

 

 

 

 

 

Is there incorrect wiring or installation

YES

 

 

 

TK1: CN514

 

 

 

 

 

TK2: CN515

 

on TK1/TK2/TK3/TK4 sensors?

 

 

 

 

 

 

 

 

 

 

 

( TK3: CN516 )

 

 

 

 

 

 

 

 

 

 

NO

 

NO

 

 

 

TK4: CN523

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are characteristics of TK2 sensor

 

 

 

 

 

 

 

 

Sensor error

 

resistance value normal?

 

*Outdoor unit temp sensor characteristics-4

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

Does OCR of MG-SW operate?

 

 

 

 

Reset OCR manually.(*2)

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After power reset

 

 

 

 

Error

 

 

 

 

 

 

 

 

 

Start a test operation in COOL or HEAT mode.

 

 

 

Replace clogging part.

 

 

 

 

 

 

 

 

 

 

 

 

TK2 sensor temp is displayed on 7-segment display with SW01/02/03=[1] [12] [2].

Check TK2 sensor temp approx. 10 minutes after compressor 2 has operated.

 

 

If low temperature continues (approximately outside temp) or temperature

 

 

does not change, a clogging of strainer of oil-equalization circuit,

 

Compressor 2

clogging of capillary or malfunction of check valve is considered.

 

 

 

 

 

 

 

 

 

 

No error

 

 

 

 

 

 

 

 

 

Strainer

 

 

 

 

Capillary tube

 

 

 

 

 

TK2

Check the clogging of SV3E valve.

Error

Oil tank

(*1)

**1 Refer to item [H07] error.

 

 

 

No error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check I/F P.C. board

 

Replace SV3E valve.

 

 

 

 

 

 

 

2If OCR operates even after manual reset of OCR, check whether the wiring to the current sensor (T02) of Comp-IPDU is correct or not.

Check code

Check code name

Cause of operation

[H16] / [d7]

TK3 temperature detective circuit error

1. Connection of TK3 sensor.

(TCC-L / AI-NET)

 

(Sub-code: 03)

2. Error in resistance value of TK3 sensor

 

 

 

 

 

 

(see 9-7 Sensor characteristics).

 

 

 

 

 

 

3. Error of SV3C valve circuit periphery

 

 

 

 

 

 

(check capillary clogging, strainer

 

 

 

 

 

 

clogging).

 

 

 

 

 

 

4. Refrigerant stagnation in case of

 

 

 

 

 

 

compressor shell.

 

 

 

 

 

 

 

 

 

Has TK3 sensor become detached?

YES

 

 

 

 

 

Correct installation of sensor.

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct wiring/installation.

 

 

 

 

 

 

Is there incorrect wiring or installation

YES

 

 

TK1: CN514

 

 

 

 

 

TK2: CN515

on TK1/TK2/TK3/TK4 sensors?

 

 

 

 

 

 

 

 

 

 

( TK3: CN516 )

 

 

 

 

 

 

 

 

 

NO

 

NO

 

 

TK4: CN523

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are characteristics of TK3 sensor

 

 

 

 

 

Sensor error ÆReplace

 

 

 

 

 

resistance value normal?

 

* Outdoor unit temp sensor characteristics-4

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

After power reset,

 

 

 

 

 

 

 

check capillary choke of SV3C valve bypass.

 

 

 

 

 

 

 

 

Error

 

Start a test operation in COOL or HEAT mode.

 

Replace clogged part (Capillary).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TK3 sensor temp is displayed on 7-segment display with SW01/02/03=[1] [13] [2].

Check TK3 sensor temp. approx. 10 minutes after compressor 2 has operated.

Strainer

 

If low temperature continues (approximately outside ambient temp.) or

 

temperature does not change, a clogging of parallel capillary is considered.

 

 

 

 

 

No error

 

 

 

 

 

SV3E valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TK3

 

 

 

Error

 

 

 

 

Check the clogging of SV3E valve.

 

 

 

 

 

 

 

Replace SV3E valve.

 

 

 

 

 

(Note 1)

(Note 1) Refer to item [H07] error.

 

 

 

 

 

 

 

 

No error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check I/F P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 150