Inverter assembly

REQUIREMENT

 

 

 

 

MRemoval of P.C.

board and

 

Wear protective clothing on your hands

 

electric parts

 

as other components may cause and

 

 

 

 

injury etc.

 

5.

Reactor

1)

Stop operation, and then turn the power

 

6.

Transformer

 

 

supply to the unit.

 

7.

Electrolytic

2)

Take off the screws (3 positions) on the

 

 

capacitor

 

terminal block installation board.

 

 

 

3)

Take off the fixing screws on each part

 

 

 

 

and then remove the cables.

Reactor, transformer and electrolytic

 

 

 

 

condenser are stored at the rear side

 

 

 

 

of the terminal block.

Caution when removing the electrolytic

capacitor (No.7)

 

2) Screw

1) Electrolytic capacitors will discharge

 

2) Screw

over time.

 

 

As the natural discharge by the electlytic

 

2) Screw

capacitor may be unavailable and

 

 

voltage may remain in some cases due

 

 

to trouble conditions, be sure to confirm

 

 

discharge of the capacitor.

 

 

2) Use a suitable resistive load (100/40W

 

Terminal block

or equivalent) to discharge the capacitor

 

installation board

 

 

or plug of the soldering iron, make

 

 

continuity and discharge between

 

 

and

poles.

 

 

Recommendation will check the voltage

 

 

with a DC volt meter.

 

 

NOTE

 

 

 

Do not discharge using a tool (e.g. screw-

5. Reactor

3) Screw

driver) as the capacitor charge can cause

 

(2 pieces)

 

an injury.

 

 

 

3) Screw

6. Transformer

 

7. Electrolytic condenser

Plug of soldering iron