No.

Part to be

Work procedure

Remarks

exchanged

 

 

 

 

 

 

 

9

Exchange of

REQUIREMENT

 

 

accumulator

 

 

 

 

Wear protective clothing on your hands as other components may cause and injury etc.

Before beginning the procedure, ensure the refrigerant has been reclaimed from the outdoor unit, using a suitable refrigerant recovery device.

1)Remove the lower cabinet (rear side).

2)Remove the fixing screws (M6 × 3 pcs.)

from the accumulator leg base board.

3)Remove the accumulator fixing board ∗ ⇔ fixing screws on accumulator (M6 × 2 pcs.)

The accumulator fixing board is fixed to the middle partition board.

(Take off only the screws, which fix the accumulator unit.)

4)Remove the pipe (brazing part) connected to the SV2 valve.

5)Remove the discharge cabinet fan and motor base.

6) Remove the accumulator cover fixing screws (M5 × 4 pcs.) of the middle partition board and then pull it upwards.

7)Using a pipe cutter, cut off the entrance/exit pipe of accumulator at the specified posi- tion. (For the cut-off position, refer to the Manual attached to the repair parts.)

8) Pull the accumulator upwards.

6) Accumulator cover

7) Cut pipe at

6)

entrance/exit ports.

 

3) Accumulator

6) Two screws each

at front and rear

fixing board

8)

 

 

Middle partition board

4) SV2 valve

Accumulator

3) Two screws

2) Three screws

 

4) Brazing part with SV2 assembly

215

Page 215
Image 215
Toshiba MMU-AP0091H service manual 215, Pull the accumulator upwards