Check code

 

Check code name

 

Cause of operation

 

 

 

 

 

[E16] / [89]

 

Connected indoor units

1.

There are 48 or more connected indoor units.

(TCC-L / AI-NET)

 

capacity over

2.

Capacity over of total connected indoor units.

 

 

 

3.

Incorrect setup of indoor/outdoor capacity

 

 

 

 

Sub-code:00 : Capacity over

01 : ~ : Number of connected indoor units

Check code

 

Check code name

 

 

Cause of operation

 

 

 

[E18] / [97/99]

Communication error between

Regular communication between indoor header

(TCC-L / AI-NET)

indoor header and follower

and follower is unavailable.

 

 

 

 

 

 

 

Are remote controller

 

NO

 

 

 

 

 

 

Correct remote controller

 

 

 

 

interconnection wires (A/B) normal?

 

 

 

interconnection wires.

 

 

 

 

 

 

 

YES

YES

Is backup operation of outdoor unit being set up?

 

NO

 

 

 

NO

Is No. of connected indoor units correct?

 

 

 

YES

 

 

 

 

 

NO

Is setup of indoor unit HP correct?

 

 

 

YES

 

 

 

 

 

NO

Is total capacity of connected

 

indoor units within 135%? (*1)

 

 

YES

 

Perform setup of no detection

for over capacity.

Excessive indoor units are connected.

Correct miswiring.

Correct HP setup.

Ensure capacity of connected

indoor units within 135% of outdoor units.

Is there any disconnection of

connector or wiring from terminal block

of indoor unit?

NO

NO

Is a group control operation?

YES

Is the power of

all indoor units turned on?

YES

Check indoor address.

YES

NO

Correct connection.

Check circuit wire.

Check power connection status

of indoor unit.

Check indoor P.C. board.

Failure ÆReplace

141

For a service P.C. board, check outdoor HP setup.

OK

(Set up jumper 9, 10, 11, and 12.)

 

 

NG

 

 

 

 

 

 

Check outdoor interface P.C. board.

Set up outdoor HP.

(Refer “How to exchange interface P.C. board”.)

(1) When capacity of the outdoor unit is 12HP, up to a maximum capacity 120% of indoor units can be connected.

Correct indoor address.

Check code

Check code name

Cause of operation

 

[E19] / [96]

Header outdoor units quantity error 1. Misconnection of interconnection cable

(TCC-L / AI-NET)

 

 

 

 

 

between indoor and outdoor

 

 

 

 

 

 

 

2. Outdoor I/F P.C. board error

 

Sub-code:00: No header unit 02: Two or more header units

 

Are communication lines (U1, U2)

YES

 

 

 

 

 

 

Connect communication line between indoor

between indoor and outdoor connected

 

 

 

 

 

 

and outdoor to one unit per 1 system.

 

to multiple outdoor units?

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

Is communication line between indoor and

 

 

Connect communication line between indoor

 

 

 

outdoor connected to one unit per 1 system?

 

 

 

and outdoor.

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reference)

 

 

 

 

Check I/F P.C. board.

 

 

 

 

 

 

 

When the power supply of the outdoor unit is first turned

 

 

 

 

 

 

 

 

 

 

on, the check code [E19 00] is displayed until the power

 

 

 

 

 

supply of the indoor units are turned on. However is not

 

 

 

 

 

an error. When the power supply of the indoor units are

 

 

 

 

 

this turned on, the check code is automatically reset.