8-3. Check at Main Power-ON

After turning on the main power of the indoor units and outdoor unit in the refrigerant line to be executed with a test operation, check the following items in outdoor and each indoor unit.

(After turning on the main power, be sure to check in order of indoor unit outdoor unit.)

If the power supply of the outdoor unit has been firstly turned on, [E19] appears on the 7-segment display on the interface P.C. board until the power supply of the indoor unit is turned on. However it is not an error.

Check on outdoor unit

1.Check that all the rotary switches, SW01, SW02, and SW03 on the interface P.C. board of the outdoor unit are set up to “1”.

2.If other error code is displayed on 7-segment [B], remove the cause of trouble referring to “9. Troubleshooting”.

3.Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the outdoor unit. (L08: Indoor address unset up)

(If the address setup operation has already finished in service time, etc, the above check code is not dis- played, and only [U1] is displayed on 7-segment display [A].)

7-segment display [A]

7-segment display [B]

Interface P.C. board

88

SW01 SW02 SW03

Check on indoor unit

1.Display check on remote controller (In case of wired remote controller)

Check that a frame as shown in the following left figure is displayed on LC display section of the remote controller.

8-4. Address Setup

After power-ON, set up the indoor address from the interface P.C. board of the outdoor unit.

(The address setup operation cannot be performed by power-ON only. )

8-4-1. Cautions

1.It requires approx. 5 minutes usually for 1 line to automatically set up address. However in some cases, it may require maximum 10 minutes.

2.It is unnecessary to operate the air conditioner for address setup.

3.Manual address setup is also available besides automatic setup.

Automatic address: Setup from SW15 on the interface P.C. board of the outdoor unit

Manual address: Setup from the weird remote controller.

(For details, refer to section 8-4-3. Address setup procedure”)

8-4-2. Address Setup and Check Procedure

Procedure

Item

 

 

Operation and check contents

 

 

 

 

 

 

 

 

 

 

 

 

1

Indoor unit power-ON

Turn on power of indoor unit in refrigerant line to which address is set up.

 

 

 

 

 

 

 

 

 

 

 

 

2

Outdoor unit power-ON

Turn on power of all the outdoor units in refrigerant line to which address is set up.

 

 

 

 

 

 

 

 

 

 

 

3

7-segment display

Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the

check

outdoor unit in the system to which address is set up.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Confirm the corresponding items in 8-4-3 Address setup procedure”, and then set up address

4

Address setup start

according to the operation procedure.

 

 

 

 

 

(Be sure that the setup operation may differ in group control or central control.)

 

 

 

 

 

 

 

 

Note) Address cannot be set up if switches are not operated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display check after

After address setup, [U1] [

] are displayed in 7-segment display section.

 

 

5

If an error code is displayed in 7-segment display [B], remove the cause of trouble referring to

setup

 

 

 

“9. Troubleshooting”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using 7-segment display function, check the system information of the scheduled system.

 

 

(This check is executed on the interface P.C. board of the outdoor unit.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rotary switch setup

7-segment display

 

 

 

 

 

 

 

 

 

 

 

 

 

6

System information

 

 

 

SW01

SW02

SW03

[A]

[B]

 

 

 

 

 

 

 

 

 

 

check after setup

 

System capacity

 

1

2

3

[No. of HP]

[HP]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. of connected outdoor unit

 

1

3

3

[Connected No. of units]

[ P]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. of connected indoor units

 

1

4

3

[Connected No. of units]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After the above checks, return rotary switches SW01, SW02, SW03 to 1/1/1.

 

 

GOOD

TEMP.

 

ON / OFF

TIMER SET

FAN

MODE

TIME

SWING/FIX

VENT

FILTER

 

 

RESET TEST SET CL

UNIT

 

NO

GOOD

TEMP.

 

ON / OFF

TIMER SET

FAN

MODE

TIME

SWING/FIX

VENT

FILTER

 

 

RESET TEST SET CL

UNIT

 

 

7-segment

Push-switch

Push-switch

Interface P.C. board

display [A]

SW04

SW05

 

 

Push-switch

 

 

 

SW15

 

 

 

7-segment

 

 

 

display [B]

Normal status

Abnormal status

(Power and operation stop)

(Power is not normally turned on.)

If a frame is not displayed as shown in the above right figure, the power of the remote controller is not normally turned on. Therefore check the following items.

Check power supply of indoor unit.

Check wiring between indoor unit and remote controller.

Check whether there is cutoff of cable around the indoor control P.C. board or not, and check connection failure of connectors.

Check failure of transformer for the indoor microcomputer.

Check indoor control P.C. board failure.

SW01 SW02 SW03

Rotary switches

Page 88