3. Data display of outdoor cycle (Displayed on each outdoor unit)

SW01

SW02

SW03

 

 

Display contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

2

Pd pressure data

Pd pressure (MPaG) is displayed with decimal data.

 

A

 

B

 

 

 

 

 

(MPaG: Approx. 1/10 value of kg/cm2G data)

 

 

 

 

 

 

 

 

 

 

P d.

 

.

 

 

 

 

 

 

 

 

 

 

2

 

Ps pressure data

Ps pressure (MPaG) is displayed with decimal data.

 

P S.

 

.

 

 

 

 

 

 

 

 

 

 

3

 

PL pressure conversion data

Estimated pressure of liquid line (MPaG) is displayed with decimal data.

P L.

 

.

 

 

 

 

 

 

 

 

 

 

 

4

 

TD1 sensor data

Temperature sensor data (°C) is displayed

 

Symbol

t d

 

1 1 1

 

 

 

 

with decimal notation.

 

 

 

 

 

 

 

 

 

 

 

Data

.

 

 

 

 

• Symbol display for 1 sec. and data display for 3 sec. are

 

 

 

 

 

 

 

 

 

 

5

 

TD2 sensor data

Symbol

t d

 

2 1 1

 

 

alternately displayed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Data is displayed in [].

 

Data

.

 

 

 

 

 

 

 

 

 

 

 

6

 

TS1 sensor data

• Negative data is displayed as [– ∗ ∗ ∗ ∗ ].

 

Symbol

t S

 

1 1 1

 

 

 

 

 

 

 

Data

.

 

7

 

TS2 sensor data

 

 

 

Symbol

tS

 

2 1 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

.

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

TE sensor data

 

 

 

Symbol

tE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

TL sensor data

 

 

 

Symbol

t L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

.

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

TO sensor data

 

 

 

Symbol

t o

 

 

 

 

 

 

 

 

 

 

Data

.

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

TK1 sensor data

 

 

 

Symbol

F 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

.

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

TK2 sensor data

 

 

 

Symbol

F 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

.

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

TK3 sensor data

 

 

 

Symbol

F 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

.

 

14

 

TK4 sensor data

 

 

 

Symbol

F 4

 

 

 

 

 

 

 

 

 

 

Data

.

 

15

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. Data display of indoor unit information (Displayed on the header unit only)

SW01

SW02

SW03

 

 

 

 

Display contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

1 to 16

1 to 3

Receiving status of

B

Receiving time: [

1], Not received: [… …

]

 

 

 

 

 

indoor BUS communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

Indoor check code

B

No check code: [– – –]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

Indoor capacity

B

0. 2,

0. 5,

0. 8,

1,

1. 2, 1. 7, 2, 2. 5,

3,

3. 2,

4, 5,

 

 

 

(HP) horse power

 

6,

8,

1 0,

1 6,

2 0

 

 

 

 

7

 

 

Indoor request command

B

Data is displayed with Hexadecimal notation [

0 to

F] : Heating

 

 

 

(S code)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

Indoor PMV opening data

B

Data is displayed with Hexadecimal notation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

Indoor TA sensor data

B

Data is displayed with Hexadecimal notation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

Indoor TF sensor data

B

Data is displayed with Hexadecimal notation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

Indoor TCJ sensor data

B

Data is displayed with Hexadecimal notation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

Indoor TC1 sensor data

B

Data is displayed with Hexadecimal notation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

Indoor TC2 sensor data

B

Data is displayed with Hexadecimal notation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE) Indoor address No. is chosen by changing SW02 and SW03.

SW03

SW02

Indoor address

7-segment display A

 

 

 

 

1

1 to 16

SW02 setup number

[01] to [16]

 

 

 

 

2

1 to 16

SW02 setup number + 16

[17] to [32]

 

 

 

 

3

1 to 16

SW02 setup number + 32

[33] to [48]

 

 

 

 

166

Page 166
Image 166
Toshiba MMU-AP0091H service manual 166, SW03 SW02 Indoor address Segment display a