7-2-2-2. Power Peak-cut Control (Expansion)

Header outdoor unit interface P.C. board

SW07

Set up Bit 1. ON Bit 2.

 

 

CN513 (BLU)

(Setup to

 

 

Header

 

 

 

unit only)

 

 

Connection cable

 

Power peak-cut

 

PJ17 (4P WHI)

 

control board

 

 

 

 

 

DC

 

 

 

1.2V

 

OFF

ON

Operation

 

 

SW2

SW1

Display

 

 

 

L1

 

 

 

Power

 

 

 

supply

 

 

 

MAX AC240V

 

 

 

Procured locally

 

Operation

The upper limit capacity of the outdoor unit is restricted based on the demand request signal from outside.

L1 : Display lamp during Power peak-cut control

SW1 : Power peak-cut ON switch 1

SW2 : Power peak-cut OFF switch 1

*1

Input signals of SW1 and SW2 are acceptable even if they are upper than pulse input (100mm. sec.) or serially made.

Be sure to prepare a contact for each terminal.

Relay contact capacity of “operation” port

Below AC240V 1A (COSØ = 100%) Below DC24V 2A (Non-inductive load)

Note) When connecting non-inductive load such as relay coil to L1 load, insert the noise surge absorber CR (In case of AC) or counter electromotive-proof diode (In case of DC) into the bypass circuit.

Power peak-cut control board: TCB-PCDM2E

Outdoor unit destination to be connected becomes the header outdoor unit (U1).

Setup at power peak-cut control (expansion) request

 

 

 

 

 

 

 

 

Outside power

Display lamp

 

Power Peak-cut request

peak-cut request

Outdoor wire interface P.C. board (SW07/ Bit 2 ON)

 

 

 

 

 

 

SW1

SW2

L1

SW07 : Bit 1 OFF

SW07 : Bit 1 ON

OFF

OFF

OFF

100%

(Normal operation)

100%

(Normal operation)

ON

OFF

ON

80%

(Upper limit restriction)

85%

(Upper limit restriction)

 

 

 

 

 

 

 

OFF

ON

ON

60%

(Upper limit restriction)

75%

(Upper limit restriction)

 

 

 

 

 

 

 

ON

ON

ON

0%

(Forced stop)

60%

(Upper limit restriction)

 

 

 

 

 

 

 

Setup positions of header outdoor

Connector position detail

unit interface P.C. board

 

 

 

CN513

 

 

 

 

Blue

 

 

 

Switch position detail

 

Bit 1

OFF

Operation stop to 60%, 80%, 100%

 

 

 

SW07

ON

ON 60% to 60%, 75%, 85%, 100%

 

 

Bit 2

ON

Power peak-cut (expansion) ON

 

 

 

 

83

Page 83
Image 83
Toshiba MMU-AP0091H Power Peak-cut Control Expansion, Setup at power peak-cut control expansion request, SW1 SW2, CN513