7. APPLIED CONTROL

7-1. Indoor Unit

7-1-1. Setup of Selecting Function in Indoor Unit

(Be sure to Execute Setup by a Wired Remote Controller)

<Procedure> Execute the setup operation while the unit stops.

3

5

6

1

TEMP.

 

ON / OFF

TIMER SET

FAN

MODE

TIME

SWING/FIX

VENT

FILTER

 

 

RESET TEST SET CL

UNIT

 

4

2

1

2

3

4

Push SET , CL , and TEST buttons simultaneously for 4 seconds or more.

The firstly displayed unit No. indicates the master indoor unit address in the group control.

In this time, the fan of the selected indoor unit is turned on.

Every pushing

UNIT

button, the indoor unit numbers in the group control are successively

 

displayed. In this time, the fan of the selected indoor unit only is turned on.

Specify the item code (DN) using the setup temperature and buttons.

Select the setup data using the timer time and buttons.

(When selecting the DN code to “33”, change the temperature indication of the unit from “°C” to “°F” on the remote controller.)

5 Push SET button. (OK if display goes on.)

To change the selected indoor unit, return to procedure 2 .

To change the item to be set up, return to procedure 3 .

6 Pushing TEST button returns the status to normal stop status.

71

Page 71
Image 71
Toshiba MMU-AP0091H service manual Procedure Execute the setup operation while the unit stops, Every pushing