11.BACKUP OPERATIONS (EMERGENCY OPERATION)

When a trouble occurs in an outdoor unit or in one of the compressors in an outdoor unit, the malfunctioning unit or compressor stops and a backup operation (emergency operation) is available through the other function- ing outdoor units and compressors. A backup operation can be set up following the procedure below.

11-1. Before Backup Operation

The method of the backup operation will differ depending on the type of trouble. Refer to the following table.

Trouble contents

Backup operation method

Setup procedure

 

 

 

When a trouble occurs on one of the compressors

Compressor backup

To item 2

in the same unit (Note 1)

 

 

 

 

 

When a trouble occurs on the both compressors

 

 

in the same unit

 

 

 

 

 

Trouble of the compressor coil

 

 

(Such as defect of compressor coil)

Outdoor unit backup or outdoor unit

To item 3 or item 4

 

 

When a trouble occurs on the refrigerating system

backup during cooling season (Note 2)

 

parts, fan system parts, or electric system parts

 

 

 

 

 

When a trouble occurs on the temperature sensor

 

 

or pressure sensor

 

 

 

 

 

(Note 1) When a trouble of the compressor coil etc has occurred, deterioration of the oil will be high. Therefore do not perform a backup operation, as other units within the system may be damaged.

(Note 2) Only one outdoor unit within a given system can be subjected to the backup procedure.

11-2. Compressor Backup Setup

Outline

When a trouble occurs on one of the two compressors, follow the procedure below. If it is necessary perform a backup operation on the other normal compressor.

Procedure

1.Turn off the main power supplies to all the units connected to the system.

2.As shown below set up the switch SW06 on the interface P.C. board on the outdoor unit on which the com- pressor has failed.

 

 

SW06

 

 

 

 

 

 

 

Bit 1

Bit 2

Bit 3

Bit 4

 

 

 

 

 

Initial setup at shipment from factory

OFF

OFF

OFF

OFF

 

 

 

 

 

No.1 compressor (Left side) is defective.

ON

OFF

OFF

OFF

 

 

 

 

 

No.2 compressor (Right front side) is defective.

OFF

ON

OFF

OFF

 

 

 

 

 

3. Turn on the main power supplies of all of the units connected to the system.

After the backup set up for the outdoor unit in cooling season is complete, check the system operates.