No.

Item

Operation explanation and applied data, etc.

 

Remarks

 

 

 

 

 

5

Oil short

This control is provided to prevent oil shortage occurring in the

 

 

 

protective

compressors of each outdoor unit.

 

 

 

control

The control is achieved by ON/OFF operation of the solenoid

 

 

 

 

valves SV3A, SV3B, SV3C and SV3D.

 

 

 

 

(1) Oil-short protective control

 

 

 

 

The oil shortage protection control function stops the outdoor

• Oil accumulated in the

 

 

unit, if an oil shortage continues for 30 minutes, after 2

 

oil separator is returned

 

 

minutes, 30 seconds the outdoor unit restarts.

 

to the compressor.

 

 

If this function is activated on 3 successive occasions, an error

 

 

 

 

check code (H07) is generated and the outdoor unit is

 

 

 

 

stopped.

 

 

 

 

 

 

 

6

Refrigerant/Oil

(1) During cooling operation, this function is executed to regularly

 

 

 

recovery control

to recover the refrigerant/oil from the indoor units and con-

 

 

 

 

necting pipe-work back to the outdoor unit.

 

 

 

 

This function is also performed to prevent stagnated refriger-

 

 

 

 

ant accumulating in the outdoor heat exchanger during low

 

 

 

 

ambient cooling.

 

 

 

 

The control is managed by the header outdoor unit.

 

 

 

 

1) Control conditions

Control for refrigerant/

 

 

• Cooling oil recovery operation is executed approximately

 

oil recovery is per-

 

 

every 2 hours.

 

formed approximately

 

 

2) Contents of control

 

every 2 hours.

 

 

Recovery lasts for

 

 

• The recovery period lasts for approximately 2 or 3

 

 

 

approximately 2 or 3

 

 

minutes though this is dependant on the system capacity.

 

 

 

 

minutes though this is

 

 

(2) Refrigerant recovery control in heating room

 

 

 

 

dependent upon the

 

 

This function is executed regularly to recover the liquid

 

 

 

 

system capacity.

 

 

refrigerant from the indoor unit.

 

 

 

 

It is also used to recover oil present in the outdoor heat

 

 

 

 

exchanger during the heating overload operation (except

 

 

 

 

during defrost operation).

 

 

 

 

The control is managed by the header outdoor unit.

 

 

 

 

1) Heating operation oil, recovery control is executed approxi-

 

 

 

 

mately every hour.

 

 

 

 

2) The period of recovery lasts for approximately 2 to 10

 

 

 

 

minutes though this is dependent upon the load condition.

 

 

 

 

(3) Control for refrigerating / whilst oil recovery in simultaneous

 

 

 

 

operation.

 

 

 

 

This function is executed to recover the refrigerating oil

 

 

 

 

accumulated in the low-pressure gas inter-unit piping.

Heating operation, oil

 

 

(regardless of all cooling operation/all heating operation).

 

 

 

recovery is executed

 

 

1) Control condition

 

 

 

 

approximately every

 

 

• When the combined time of the compressor-ON has

 

hour.

 

 

reached 95 minutes in simultaneous operation.

• Recovery lasts for

 

 

2) Control contents

 

approximately 2 to 10

 

 

When the conditions have been satisfied, upon changing

 

minutes though this is

 

 

 

dependent upon the

 

 

the indoor unit mode from heating to cooling, (stop the

 

 

 

 

load condition.

 

 

indoor fan) the oil is recovered for a period between 2

 

 

 

 

 

 

 

minutes 30 seconds to 10 minutes. The indoor unit in

 

 

 

 

cooling operation continues operation.

 

 

 

 

 

 

 

7

Defrost control

(1) Defrost start condition

During the defrost

 

(Reverse cycle

The defrost function is initiated when the measurement

 

operation, all solenoid

 

defrost method)

temperature taken from the TE sensor is lower than -2°C for a

 

4-way valves are OFF

 

 

period of 25 minutes after compressor initial start up and 55

 

and all compressors

 

 

minutes after subsequent start ups.

 

are operating.

 

 

(2) Contents of control

 

 

 

 

• If the outdoor units are combined, the minimum duration for

 

 

 

 

the defrost operation is 2 minutes.

 

 

 

 

(3) Defrost stop condition

 

 

 

 

• The outdoor fan speed and compressor inverter frequency

 

 

 

 

are determined by the measurement of Pd pressure during

 

 

 

 

defrost operation.

 

 

 

 

 

 

 

66

Page 66
Image 66
Toshiba MMU-AP0091H service manual Operation explanation and applied data, etc Remarks