Toshiba MMU-AP0091H service manual Check Method, Check code list, 117

Models: MMU-AP0091H

1 228
Download 228 pages 22.05 Kb
Page 117
Image 117

9-2. Check Method

If an trouble occurs, the error code can be retrieved from the main remote controller/central remote controller (LCD display) or the header unit interface P.C. board (7-segment display). Using this self diagnostic function, the trouble can be identified using the table below.

Check code list

The following list shows all fault codes.

If check code is from indoor remote controller: See “Main remote controller display” in the list.

If check code is from outdoor unit: See “Outdoor 7-segment display” in the list.

If check code is from AI-NET central control remote controller: See “AI-NET central control display” in the list.

If check code is from indoor unit with wireless remote controller: See “Sensor display of receiving unit” in the list.

IPDU: Intelligent Power Drive Unit

¡: Lighting, ¤: Flashing, l : Goes off

ALT.: Flashing is alternately when there are two flashing LED.

SIM: Simultaneous flashing when there are two flashing LED

Check code

Wireless remote controller

Main

Outdoor 7-segment display

 

Sensor block display

 

 

AI-NET central

of receiving unit

Check code name

Detecting device

remote

 

 

 

 

 

 

 

 

 

controller

 

Auxiliary code

control display

Operation

Timer

Ready

 

 

display

 

 

 

 

Flash

 

 

E01

¤ l

l

Communication error between indoor and remote

Remote controller

controller (Detected at remote controller side)

E02

¤ l

l

Remote controller transmission error

Remote controller

E03

97

¤ l

l

Communication error between indoor and remote

Indoor

controller (Detected at indoor side)

E04

04

l

l

¤

Communication circuit error between indoor/outdoor

Indoor

(Detected at indoor side)

E06

E06

No. of indoor units in which

04

l

l

¤

Decrease of No. of indoor units

I/F

sensor has been normally

 

 

received

 

 

 

 

 

E07

l

l

¤

Communication circuit error between indoor/outdoor

I/F

(Detected at outdoor side)

E08

E08

Duplicated indoor addresses

96

¤ l

l

Duplicated indoor addresses

Indoor / I/F

E09

99

¤ l

l

Duplicated main remote controllers

Remote controller

E10

CF

¤ l

l

Communication error between indoor MCU

Indoor

 

 

01: Indoor/Outdoor

 

¤ l

 

 

 

E12

E12

communication

42

l

Automatic address start error

I/F

02: Communication between

 

 

outdoor units

 

 

 

¤

 

 

E15

E15

42

l

l

Indoor is nothing during automatic addressing

I/F

E16

E16

00: Capacity over

89

l

l

¤

Capacity over / No. of connected indoor units

I/F

01 ~: No. of connected units

E18

97, 99

¤ l

l

Communication error between indoor units

Indoor

E19

E19

00: Header is nothing

96

l

l

¤

Outdoor header units quantity error

I/F

02: Two or more header units

 

 

01: Outdoor of other line

 

 

 

¤

 

 

E20

E20

connected

42

l

l

Other line connected during automatic address

I/F

02: Indoor of other line

 

 

connected

 

 

 

¤

 

 

E23

E23

15

l

l

Sending error in communication between outdoor units

I/F

E25

E25

15

l

l

¤

Duplicated follower outdoor addresses

I/F

E26

E26

No. of outdoor units which

15

l

l

¤

Decrease of No. of connected outdoor units

I/F

received signal normally

E28

E28

Detected outdoor unit number

d2

l

l

¤

Follower outdoor unit error

I/F

 

 

01: IPDU1 error

 

 

 

 

 

 

 

 

02: IPDU2 error

 

 

 

 

 

 

 

 

03: IPDU1, 2 error

 

 

 

¤

 

 

E31

E31

04: Fan IPDU error

CF

l

l

IPDU communication error

I/F

 

 

05: IPDU + Fan IPDU error

 

 

 

 

 

 

 

 

06: IPDU2 + Fan IPDU error

 

 

 

 

 

 

 

 

07: All IPDU error

 

 

 

 

 

 

 

 

 

 

 

 

117

 

 

Page 117
Image 117
Toshiba MMU-AP0091H service manual Check Method, Check code list, 117