9-5. Diagnosis Procedure for Each Check Code

Check code

Check code name

 

Cause of operation

 

 

 

[E01] / [–]

Communication error between

1. Remote controller interconnecting cable

(TCC-L / AI-NET)

indoor and remote controller

 

error

 

(Detected at remote controller side)

2. Indoor power supply error

 

 

3.

Indoor P.C. board error

 

 

4.

Remote controller address setup error

 

 

5.

Remote controller P.C. board error

 

 

 

 

Check code

Check code name

Cause of operation

 

 

 

[E03] / [97]

Communication error between

No communication from remote controller and

(TCC-L / AI-NET)

indoor and remote controller

communication adaptor

 

(Detected at indoor side)

 

 

 

 

This error is detected when the indoor unit cannot receive a signal from the remote controller. Check communication wiring of the remote controllers A and B.

As communication is impossible, this fault code [E03] is not displayed on the main remote controller. It is displayed on TCC-LINK central controller.

Is the interconnection cable of

NO

remote controllers (A/B) normal?

 

 

YES

 

 

 

Is there no disconnection or

YES

connector contact error on harness out

 

of terminal block of indoor unit?

 

 

NO

 

 

 

 

 

 

NO

Is a group control operation?

YES

Correct interconnection cable of remote controller.

Correct connection and check circuit cabling.

Check code

Check code name

 

Cause of operation

 

 

 

 

[E04] / [04]

Indoor/Outdoor

1.

Power of outdoor unit was firstly turned on.

(TCC-L / AI-NET)

communication circuit error

2.

Connection error of communication line

 

(Detected at indoor side)

 

between indoor and outdoor

 

 

3.

Terminal resistance setup error on outdoor

 

 

 

header unit.

 

 

4.

Address setup error

 

 

 

 

Is power of each indoor unit turned on?

NO

Check power connection status of indoor unit. (Turn on power again.)

Was power turned on in order

NO

 

of indoor unit Æoutdoor unit?

 

Turn on power again in order of indoor unit Æoutdoor unit.

138

 

YES

 

Is power applied to remote controller?

NO

AB terminals: Approx. DC18V

 

 

YES

 

Check indoor P.C. board.

Defect ÆReplace

 

YES

 

 

 

NO

Is connection (U1/U2 terminals) of

indoor/outdoor interconnection cable normal?

 

Correct interconnection cable.

Are two remote controllers used

YES

Change one to main/other to sub.

YES

without the correct identification?

NO

(Remote controller address connector)

Check remote controller P.C. board.

Defect ÆReplace

Is the end terminal resistance

NO

setup of outdoor unit normal?

 

 

YES

 

 

 

 

 

NO

Is address setup correct?

 

 

 

YES

 

 

 

 

 

 

Correct the end terminal resistance setup.

Set up address again.

Check code

Check code name

Cause of operation

[E02] / [–]

Remote controller sending error Signal could not be sent to indoor unit.

(TCC-L / AI-NET)

Check the communication wire of the remote

 

controller.

* It is not displayed on 7-segment display of the central control controller.

Is power applied to fuse (F03)

NO

on indoor P.C. board?

 

 

YES

 

 

 

 

 

YES

Is there no noise, etc?

 

 

 

NO

 

 

 

 

 

 

Check connection of interconnection cable between indoor and outdoor is correct, and then connect communication line connector on indoor P.C. board (CN40) to CN44 (EMG).

Check noise etc. and eliminate it if any.

Is communication wiring between

NO

remote controller and indoor unit correct?

 

 

YES

 

 

 

 

 

 

ÆSending circuit error of the remote controller Replace remote controller.

Correct the communication wiring.

Check indoor P.C. board.

Defect ÆReplace

For details, refer to “Troubleshooting in test operation”.