124

9-4. Check Code and Check Position Displayed on the Remote Controller and Outdoor Unit (7-Segment Display of Interface)

 

Check code

 

 

 

 

 

 

 

 

 

 

 

 

Detected

Check code name

Status

Error detection condition

Check item (position)

Main

Outdoor 7-segment display

AI-NET

 

 

position

remote

 

 

central control

 

 

 

 

 

controller

Check code

Sub-code

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E01

 

Remote

Communication error between

Corresponding

Communication interrupted

• Check remote controller inter-unit cable (A/B).

 

 

 

 

 

controller

indoor and remote controller

unit only stops.

between indoor P.C. board

• Check disconnection, connector contact error.

 

 

 

 

 

 

(Detected at remote controller side)

 

and remote controller.

• Check indoor power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check indoor P.C. board error.

 

 

 

 

 

 

 

 

 

• Check remote controller address setup.

 

 

 

 

 

 

 

 

 

(When two remote controllers operate)

 

 

 

 

 

 

 

 

 

• Check remote controller P.C. board.

 

 

 

 

 

 

 

 

 

 

E02

 

Remote

Remote controller sending error

Corresponding

Signal could not be sent from

• Check the communication wire of remote controller: Exchange remote

 

 

 

 

 

controller

 

unit only stops.

remote controller to indoor

controller.

 

 

 

 

 

 

 

 

unit.

 

 

 

 

 

 

 

 

 

 

 

E03

97

 

Indoor unit

Communication error between

Corresponding

No communication from

• Check remote controller and communication adapter wiring.

 

 

 

 

 

 

indoor and remote controller

unit only stops.

remote controller (including

 

 

 

 

 

 

 

(Detected at indoor side)

 

wireless) and communication

 

 

 

 

 

 

 

 

 

adapter.

 

 

 

 

 

 

 

 

 

 

 

E04

4

 

Indoor unit

Indoor/outdoor communication

Corresponding

Indoor unit does not receive

• Check power-ON order of indoor/outdoor.

 

 

 

 

 

 

circuit error

unit only stops.

communication from outdoor

• Check indoor address setup.

 

 

 

 

 

 

(Detected at indoor side)

 

unit.

• Check inter-unit cabling between indoor and outdoor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check outdoor end terminal resistance setup (SW30-2).

 

 

 

 

 

 

 

 

 

 

E06

E06

No. of indoor

4

 

I/F

Decreased number of indoor units

All stop

When signal is not sent for a

• Check the power supply of indoor unit. (Power-ON)

 

 

units which

 

 

 

 

 

certain period from the indoor

• Check connection of communication line between indoor and outdoor.

 

 

received signal

 

 

 

 

 

unit which has been used to

• Check connector connection for communication in indoor P.C. board.

 

 

normally

 

 

 

 

 

send signals, [E06] is

 

 

 

 

 

 

 

• Check connector connection for communication in outdoor P.C. board.

 

 

 

 

 

 

 

 

normally displayed.

 

 

 

 

 

 

 

 

• Check indoor P.C. board failure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check outdoor P.C. board (I/F) failure.

 

 

 

 

 

 

 

 

 

 

E07

 

I/F

Indoor/outdoor communication

All stop

Transmission from outdoor to

• Check outdoor terminator resistor setup (SW30-2).

 

 

 

 

 

 

circuit error

 

indoor cannot continue for 30

• Check the communication connection between indoor and outdoor.

 

 

 

 

 

 

(Detected at outdoor side)

 

seconds.

 

 

 

 

 

 

 

 

 

 

 

E08

E08

Duplicated

96

 

Indoor

Duplicated indoor addresses

All stop

Multiple indoor unit address

• Check indoor address.

 

 

indoor

 

 

I/F

 

 

setup are duplicated.

• Check the change of remote controller connection (Group / individual)

 

 

addresses

 

 

 

 

 

 

after setup of indoor address.

 

 

 

 

 

 

 

 

 

 

E09

99

 

Remote

Duplicated master remote

Corresponding

In 2-remote controller control

• Check remote controller setup.

 

 

 

 

 

controller

controllers

unit only stops.

(including wireless), both are

• Check remote controller P.C. board.

 

 

 

 

 

 

 

 

setup as master

 

 

 

 

 

 

 

 

 

(Header indoor unit stops and

 

 

 

 

 

 

 

 

 

other indoor unit is operating.)

 

 

 

 

 

 

 

 

 

 

 

E10

CF

 

Indoor unit

Communication error between

Corresponding

There is any trouble in power

• Indoor P.C. board failure

 

 

 

 

 

 

indoor P.C. board assembly

unit only stops.

line.

 

 

 

 

 

 

 

 

 

 

 