4.3.1Recommended Wire Size and Torque Requirements For UPS Input and Output Terminals
Minimum Wire Size and Torque Requirements
UPS Input and Output Terminals 50 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
| INPUT: |
|
|
|
| OUTPUT: |
|
| |
(H1) (H2) (H3) | AWG |
|
| NEUTRAL |
| (L1)(L2)(L3) | AWG | NEUTRAL | Tightening |
|
|
|
| AWG |
|
|
| AWG | Torque |
208 | 1/0 |
|
| 250MCM | 208/120 | 1/0 | 250MCM | 200 | |
220 | 1/0 |
| 4/0 |
| 220/127 | 1/0 | 4/0 | 200 | |
240 | 1 |
|
| N/A | 240 | 1 | N/A | 200 | |
380 | 4 |
| 1/0 |
| 380/220 | 4 | 1/0 | 200 | |
400 | 4 |
| 1/0 |
| 400/230 | 4 | 1/0 | 200 | |
415 | 4 |
| 1 |
| 415/240 | 4 | 1 | 200 | |
480 | 6 |
| 2 |
| 480/277 | 6 | 2 | 200 | |
600 | 6 |
|
| N/A | 600 | 6 | N/A | 200 |
All wire sizes are per the NEC. Maximum Wire Size for Input and Output is 1/0 AWG.
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size for Neutral is 250MCM.
| Input/ Output (GND) |
|
| 50 kVA | |
|
| AWG |
| Tightening Torque | |
| 6 |
| 200 | ||
| 6 |
| 200 | ||
| 600VAC | 8 |
| 200 |
| Battery (+) / |
|
| 50 kVA | |
|
| AWG |
| Tightening Torque | |
(+) |
| 250MCM |
| 200 |
Maximum Wire Size for Battery is 250MCM.
Minimum Wire Size and Torque requirements
UPS Optional Bypass Input Terminals TB4 50 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
|
| Phase: (A) (B) (C) |
|
| 50 kVA |
|
|
|
| Input: (H1) (H2) (H3) |
| AWG | NEUTRAL AWG | Tightening Torque |
|
208/120 |
| 1/0 | 250MCM | 200 |
| ||
220 |
| 1/0 | 4/0 | 200 |
| ||
240 |
| 1 | N/A | 200 |
| ||
380 |
| 4 | 1/0 | 200 |
| ||
400 |
| 4 | 1/0 | 200 |
| ||
415 |
| 4 | 1 | 200 |
| ||
480 |
| 6 | 2 | 200 |
| ||
600 |
| 6 | N/A | 200 |
|
Maximum Wire Size for Input is 1/0 AWG. Maximum Wire Size for Neutral is 250MCM.
25