TOSHIBA
10
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation, maintenance, and
operation of the UPS and its batteries to assure safe and proper operation
1. Turn off, lockout, and tagout all power sources before connecting the power wiring to the equipment
or when performing maintenance.
2. Hardwire type UPS units are not equipped with an over-current protection device, nor do they have
an output disconnect for the ac output. Therefore, a user-installed circuit breaker should be provided
between the UPS output and the load input.
3. Battery servicing should be performed by a qualified Toshiba Representative only.
4. Unauthorized personnel should not service batteries.
5. Contact your nearest Toshiba authorized service center for battery replacement.

Qualified Personnel ONLY!

Qualified Personnel is one that has the skills and knowledge relating to the construction, installation,
operation, and maintenance of the electrical equipment and has received safety training on the
hazards involved (Refer to the latest edition of NFPA 70E for additional safety requirements).

Qualified Personnel shall:

1. Have read the entire operation manual.
2. Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and
equipment, and clear faults in accordance with established safety practices.
3. Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves,
hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety
practices.
4. Be trained in rendering first aid.
5. Be knowledgeable of batteries and the required handling and maintenance precautions.

For further information on workplace safety visit www.osha.gov.

Refer to the Battery System Manual for details on operating and maintaining the battery units for each
system.
UPS System’s output is not equipped with an over-current protection device, or an output disconnect for the
AC output; therefore, a circuit breaker should be provided, by the user, between the UPS output and the
critical load input. This device should be rated as follows:
15 kVA 25 kVA 30 kVA 33 kVA 50 kVA
Rated Output Rating Rating Rating Rating Rating
208/120 VAC 240V, 60A 240V, 90A 240V, 110A 240V, 120A 240V, 175A
220/127 VAC 240V, 50A 240V, 90A 240V, 110A 240V, 120A 240V, 175A
240 240V, 50A 240V, 80A 240V, 90A 240V, 100A 240V, 175A
380/220 480V, 30A 480V, 50A 480V, 60A 480V, 70A 480V, 100A
480/277 480V, 25A 480V, 40A 480V, 50V 480V, 50A 480V, 80A
600 600V, 20A 600V, 35A 600V, 40A 600V, 40A 600V, 70A