Chapter 4 Parameters

The following is an example of CRC generation using C language. The function takes two arguments:

Unsigned char* data Å a pointer to the message buffer

Unsigned char length Å the quantity of bytes in the message buffer The function returns the CRC value as a type of unsigned integer. Unsigned int crc_chk(unsigned char* data, unsigned char length){

int j;

unsigned int reg_crc=0xFFFF; while(length--){

reg_crc ^= *data++; for(j=0;j<8;j++){

if(reg_crc & 0x01){ /* LSB(b0)=1 */ reg_crc=(reg_crc>>1) ^ 0xA001;

}else{ reg_crc=reg_crc >>1;

}

}

}

return reg_crc;

}

3.5 Address list

The contents of available addresses are shown as below:

Content

AC drive

Parameters

Command Write only

Address

 

Function

 

GG means parameter group, nn means parameter number,

GGnn

for example, the address of Pr 4-01 is 0401H. Referencing to

chapter 5 for the function of each parameter. When reading

H

parameter by command code 03H, only one parameter can

 

be read at one time.

 

 

0: No function

2000H

Bit 0-3

1: Stop

2: Run

 

 

 

 

3: Jog + Run

 

 

00B: No function

 

Bit 4-5

01B: FWD

 

10B: REV

 

 

 

 

11B: Change direction

 

 

00B: 1st accel/decel

 

Bit 6-7

01B: 2nd accel/decel

 

10B: 3rd accel/decel

 

 

 

 

11B: 4th accel/decel

 

Bit 8-11

Represented 16 step speeds.

Revision Nov. 2008, VLE1, SW V1.03

4-93