Chapter 4 Parameters

 

 

 

06-26

PTC (Positive Temperature Coefficient) Detection Selection

 

Control

VF

VFPG

SVC FOCPG TQCPG FOCPM

Factory setting: 0

mode

 

 

 

 

 

 

Settings

0

 

Warn and keep operating

 

 

 

1

 

Warn and ramp to stop

 

 

 

 

 

 

 

It is used to set the treatment after detecting PTC.

06-27

PTC Level

 

 

Unit: 0.1

Control

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 50.0

mode

 

 

 

 

 

 

Settings

0.0 to 100.0%

 

 

 

It is used to set the PTC level, and the corresponding value for 100% is max. analog input

value.

 

 

 

 

 

 

 

06-28

Filter Time for PTC Detection

Unit: 0.01

Control

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 0.20

mode

 

 

 

 

 

 

Settings

0.00 to 10.00 sec

 

 

 

 

 

 

 

 

 

 

 

06-29

EPS Voltage

 

 

Unit: 0.1

Control

VF

VFPG

SVC

FOCPG TQCPG FOCPM

 

mode

 

 

 

 

 

 

Settings

48.0~375.0Vdc

Factory setting: 48.0

 

 

96.0~750.0Vdc

Factory setting: 96.0

It is used with the setting 43 (EPS function) of Pr.02-01~02-08 (Multi-Function Input Command).

4-74

Revision Nov. 2008, VLE1, SW V1.03