Chapter 4 Parameters

 

 

 

 

01-04

2nd Output Voltage Setting

 

 

Unit: 0.1

 

Control

VF

VFPG

 

 

 

 

mode

 

 

 

 

 

 

 

Settings

230V series

0.1 to 255.0V

Factory Setting: 5.0

 

 

 

460V series

0.1 to 510.0V

Factory Setting: 10.0

 

 

 

 

 

 

 

01-05

3rd Output Frequency Setting

 

 

Unit: 0.01

 

Control

VF

VFPG

 

 

Factory setting: 0.50

 

mode

 

 

 

 

 

 

 

Settings

0.00~120.00Hz

 

 

 

 

 

 

 

 

 

01-06

3rd Output Voltage Setting

 

 

Unit: 0.1

 

Control

VF

VFPG

 

 

 

 

mode

 

 

 

 

 

 

 

Settings

230V series

0.1 to 255.0V

Factory Setting: 5.0

 

 

 

460V series

0.1 to 510.0V

Factory Setting: 10.0

 

 

 

 

 

 

01-07

4th Output Frequency Setting

 

 

Unit: 0.01

 

Control

VF

VFPG SVC FOCPG TQCPG

 

 

mode

 

 

 

 

 

 

 

Settings

0.00~120.00Hz

 

 

Factory Setting: 0.00

 

 

 

 

 

01-08

4th Output Voltage Setting

 

 

Unit: 0.1

 

Control

VF

VFPG

 

 

 

 

mode

 

 

 

 

 

 

 

Settings

230V series

0.1 to 255.0V

Factory Setting: 0.0

 

 

 

460V series

0.1 to 510.0V

 

Factory Setting: 0.0

V/f curve setting is usually set by the motor’s allowable loading characteristics. Pay special attention to the motor’s heat dissipation, dynamic balance, and bearing lubricity, if the loading characteristics exceed the loading limit of the motor.

For the V/f curve setting, it should be Pr.01-01Pr.01-03Pr.01-05Pr.01-07. There is no limit for the voltage setting, but a high voltage at the low frequency may cause motor damage, overheat, stall prevention or over-current protection. Therefore, please use the low voltage at the low frequency to prevent motor damage.

4-30

Revision Nov. 2008, VLE1, SW V1.03