Delta Electronics VFD-VL manual Specifications for Brake Unit

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 203
Image 203

Appendix B Accessories

Order P/N: BR1K0W050, BR1K2W008, BR1K2W6P8, BR1K5W005, BR1K5W040

B.1.2 Specifications for Brake Unit

 

 

230V Series

 

460V Series

 

 

2015

2022

4030

4045

4132

 

Max. Motor Power (kW)

15

22

30

45

132

 

Max. Peak Discharge Current

40

60

40

60

240

 

(A) 10%ED

Output Rating

 

 

 

 

 

Continuous Discharge Current

15

20

15

18

75

(A)

330/345/360/380

660/690/720/760/ 618/642/667/690

Brake Start-up Voltage (DC)

 

 

 

/400/415±3V

800/830±6V

/725/750±6V

Input Rating

DC Voltage

200~400VDC

 

400~800VDC

 

 

 

 

 

 

 

Protection

 

 

Heat Sink Overheat

Temperature over +95°C (203 oF)

 

 

 

 

 

 

 

 

 

Alarm Output

Relay contact 5A 120VAC/28VDC (RA, RB, RC)

 

 

 

 

 

 

 

 

Power Charge Display

Blackout until bus (+~-) voltage is below 50VDC

 

 

 

 

 

 

 

 

Environment

 

 

Installation Location

Indoor (no corrosive gases, metallic dust)

 

 

 

 

Operating Temperature

-10°C +50°C (14oF to 122oF)

 

 

 

 

 

Storage Temperature

-20°C +60°C (-4oF to 140oF)

 

 

 

 

 

Humidity

90% Non-condensing

 

 

 

 

 

Vibration

2m/s2 (0.2G) at 20~50Hz

 

 

 

 

 

 

 

 

 

Wall-mounted Enclosed Type

IP50

IP10

B-6

Revision Nov. 2008, VLE1, SW V1.03