Delta Electronics VFD-VL manual Group 7 Special Parameters

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 68
Image 68

Chapter 4 Parameters

Group 7 Special Parameters

 

 

Pr.

Explanation

Settings

Factory

VF

VFPG

SVC

FOCPG

TQCPG

FOCPM

 

 

 

 

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07-00

Brake Chopper Level

230V: 350.0~450.0Vdc

380.0

 

 

 

 

460V: 700.0~900.0Vdc

760.0

 

 

 

 

 

 

 

07-01

Brake ED Value Setting

0~100%

100

 

 

 

 

 

 

 

 

 

 

07-02

DC Brake Current Level

0~100%

0

 

 

 

 

07-03

DC Brake Time during Start-

0.0~60.0 sec

0.0

 

up

 

 

 

 

 

 

 

 

 

07-04

DC Brake Time during

0.0~60.0 sec

0.0

 

Stopping

 

 

 

 

 

 

 

 

07-05

Start-point for DC Brake

0.00~120.00Hz

0.00

 

 

 

 

 

 

 

 

 

 

 

 

 

07-06

DC Brake Proportional Gain

1~500Hz

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07-07

Dwell Time at Accel.

0.00~600.00sec

0.00

 

 

 

 

 

 

 

 

 

 

 

 

07-08

Dwell Frequency at Accel.

0.00~120.00Hz

0.00

 

 

 

 

 

 

 

 

 

 

 

 

07-09

Dwell Time at Decel.

0.00~600.00sec

0.00

 

 

 

 

 

 

 

 

 

 

 

 

07-10

Dwell Frequency at Decel.

0.00~120.00Hz

0.00

 

 

 

 

 

 

 

 

 

 

 

 

07-11

Fan Control

0: Fan always ON

2

 

 

 

 

1: 1 minute after AC motor drive stops, fan will be OFF

 

 

 

 

 

 

 

 

 

 

 

2: AC motor drive runs and fan ON, AC motor drive stops and

 

 

 

 

 

 

 

 

 

 

 

fan OFF

 

 

 

 

 

 

 

 

 

 

 

3: Fan ON to run when preliminary heat sink temperature

 

 

 

 

 

 

 

 

 

 

 

attained

 

 

 

 

 

 

 

 

 

 

 

4: Fan always OFF

 

 

 

 

 

 

 

 

07-12

Torque Command

-100.0~100.0% (Pr. 07-14 setting=100%)

0.0

 

 

 

 

 

07-13

Torque Command Source

0: Digital keypad (KPVL-CC01)

2

 

 

 

 

 

 

 

 

 

1: RS485 serial communication (RJ-11)

 

 

 

 

 

 

 

 

 

 

 

2: Analog signal (Pr.03-00)

 

 

 

 

 

 

 

 

07-14

Maximum Torque Command

0~500%

100

07-15

Filter Time of Torque

0.000~1.000 sec

0.000

 

 

 

 

 

 

 

 

Command

 

 

 

 

 

 

 

 

 

07-16

Speed Limit Selection

0: By Pr.07-17 and Pr.07-18

0

 

 

 

 

 

 

 

 

 

1: Frequency command source (Pr.00-14)

 

 

 

 

 

 

 

 

07-17

Torque Mode +Speed Limit

0~120%

10

 

 

 

 

 

 

07-18

Torque Mode-Speed Limit

0~120%

10

 

 

 

 

 

07-19

Source of Torque Offset

0: Disable

0

 

 

 

 

 

 

1: Analog input (Pr.03-00)

 

 

 

 

 

 

 

 

 

 

 

2: Torque offset setting (Pr.07-20)

 

 

 

 

 

 

 

 

 

 

 

3: Control by external terminal (by Pr.07-21 to Pr.07-23)

 

 

 

 

 

 

 

07-20

Torque Offset Setting

0.0~100.0%

0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07-21

High Torque Offset

0.0~100.0%

30.0

 

 

 

07-22

Middle Torque Offset

0.0~100.0%

20.0

 

 

 

07-23

Low Torque Offset

0.0~100.0%

10.0

 

 

 

07-24

Forward Motor Torque Limit

0~500%

200

 

 

 

07-25

Forward Regenerative

0~500%

200

 

 

 

 

 

 

Torque Limit

 

 

 

 

 

 

 

 

 

07-26

Reverse Motor Torque Limit

0~500%

200

 

 

 

07-27

Reverse Regenerative

0~500%

200

 

 

 

 

 

 

Torque Limit

 

 

 

 

 

 

 

 

07-28

Emergency Stop (EF) &

0: Coast to stop

0

 

 

 

Forced Stop Selection

1: By deceleration Time 1

 

 

 

 

 

 

 

 

 

 

 

2: By deceleration Time 2

 

 

 

 

 

 

 

 

 

 

 

3: By deceleration Time 3

 

 

 

 

 

 

 

 

 

 

 

4: By deceleration Time 4

 

 

 

 

 

 

 

 

 

 

 

5: By Pr.01-31

 

 

 

 

 

 

 

07-29

Time for Decreasing Torque

0.000~1.000 sec

0.000

 

 

 

 

 

 

at Stop

 

 

 

 

 

 

 

 

Revision Nov. 2008, VLE1, SW V1.03

4-13