Delta Electronics VFD-VL Off, Rev, MI1, MI2, MI3, MI4, MI5, MI6, MI7, MI8, Com, Dcm, Mra, Mrc

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 36
Image 36

Terminal symbols and functions

 

Chapter 2 Installation and Wiring

 

 

 

 

Terminal

Terminal Function

 

Factory Settings (SINK)

 

 

Symbol

 

ON: Connect to DCM

 

 

 

 

 

 

FWD

Forward-Stop Command

ON:

RUN in FWD direction

 

OFF:

Stop acc. to Stop Method

 

 

 

 

 

 

 

 

 

REV

Reverse-Stop Command

ON:

RUN in REV direction

 

OFF:

Stop acc. to Stop Method

 

 

 

 

 

 

 

 

 

 

MI1

Multi-function Input 1

 

 

 

 

 

 

 

 

 

 

MI2

Multi-function Input 2

 

 

 

 

 

 

Refer to Pr.02-01 to Pr.02-08 for programming

 

MI3

Multi-function Input 3

 

the Multi-function Inputs.

 

 

 

 

MI4

Multi-function Input 4

ON: input voltage is 24Vdc (Max. 30Vdc), input

 

 

 

impedance is 3.75kΩ

 

 

 

 

MI5

Multi-function Input 5

OFF: leakage current tolerance is 10μA.

 

 

 

MI8: when JP1 is inserted, this function is

 

MI6

Multi-function Input 6

 

disabled.

 

 

 

 

 

 

 

 

MI7

Multi-function Input 7

 

 

 

 

 

 

 

 

 

 

MI8

Multi-function Input 8

 

 

 

 

 

 

 

 

COM

Digital Signal Common

Common for digital inputs and used for SINK

 

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+E24V

Digital Signal Common

+24V 80mA

 

(Source)

 

 

 

 

 

 

 

 

 

 

DCM

Digital Signal Common (Sink)

Common for digital inputs and used for SINK

 

mode

 

 

 

 

 

 

 

 

 

RA

Multi-function Relay Output 1

Resistive Load:

 

(N.O.) a

 

 

 

5A(N.O.)/3A(N.C.) 240VAC

 

RB

Multi-function Relay Output 1

 

5A(N.O.)/3A(N.C.) 24VDC

 

(N.C.) b

 

 

Inductive Load:

 

 

 

 

RC

Multi-function Relay Common

 

1.5A(N.O.)/0.5A(N.C.) 240VAC

 

 

 

1.5A(N.O.)/0.5A(N.C.) 24VDC

 

MRA

Multi-function Relay Output 2

 

To output monitor signal, including in operation,

 

(N.O.) a

 

 

frequency arrival, overload and etc.

 

 

 

 

 

 

 

MRC

Multi-function Relay Common

Refer to Pr.02-11~02-12 for programming

 

 

 

 

 

 

 

+10V

Potentiometer Power Supply

-10~+10VDC 20mA (variable resistor 3-5kohm)

 

 

 

-10V

 

 

 

 

 

 

 

 

 

 

 

 

MCM

Multi-function Output

Max. 48VDC 50mA

 

Common (Photocoupler)

 

 

 

 

 

 

 

 

 

 

 

Revision Nov. 2008, VLE1, SW V1.03

2-11

Page 36
Image 36
Delta Electronics VFD-VL manual Off, Rev, MI1, MI2, MI3, MI4, MI5, MI6, MI7, MI8, Com, Dcm, Mra, Mrc, Mcm