Delta Electronics VFD-VL manual Operation and Start Up

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 51
Image 51

Chapter 3 Operation and Start Up

„Setting the acceleration/deceleration with Pr.01-23 and the setting 08 (the 1st, 2nd acceleration/deceleration time selection) and 09 (the 3rd, 4th acceleration/deceleration time selection) of multi-function input command Pr.02-01~02-08.

„Settings of acceleration/deceleration time: Pr.01-12~Pr.01-19

Settings of Pr.01-12 to

Accel Time 1

0.00~600.00 sec

Pr.01-19

Decel Time 1

0.00~600.00 sec

 

 

Accel Time 2

0.00~600.00 sec

 

Decel Time 2

0.00~600.00 sec

 

Accel Time 3

0.00~600.00 sec

 

Decel Time 3

0.00~600.00 sec

 

Accel Time 4

0.00~600.00 sec

 

Decel Time 4

0.00~600.00 sec

NOTE: it is recommended to set the acceleration/deceleration time to the small value in the trial run and execute smooth test after all the actions are correct.

„Settings of S curve: Pr.01-24~Pr.01-30

Settings of Pr.01-24 to

S-curve for Acceleration

0.00~25.00 sec

Pr.01-30

Departure Time S1

 

 

S-curve for Acceleration

0.00~25.00 sec

 

Arrival Time S2

 

 

S-curve for Deceleration

0.00~25.00 sec

 

Departure Time S3

 

 

S-curve for Deceleration

0.00~25.00 sec

 

Arrival Time S4

 

 

 

0: Output waiting

 

Mode Selection when

1: Zero-speed operation

 

Frequency < Fmin

2: Fmin (4th output

 

 

 

 

frequency setting)

 

Switch Frequency for

0.00~120.00Hz

 

S3/S4 Changes to S5

 

 

S-curve for Deceleration

0.00~25.00 sec

 

Arrival Time S5

 

NOTE: it is recommended to set the S curve time to 0 in trial run and execute smooth test after all the actions are correct.

3-12

Revision Nov. 2008, VLE1, SW V1.03

Page 51
Image 51
Delta Electronics VFD-VL manual Operation and Start Up