Delta Electronics VFD-VL DC voltage Low voltage level Battery voltage, Run, Valve, About 2 sec

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 29
Image 29

Chapter 2 Installation and Wiring

Figure 4 Apply to two batteries with main battery voltage is lower than 280Vdc

1

AC motor driv e

 

Main

2

R /L1

 

power

 

 

 

 

48V dc (230V Se rie s)

3

 

 

S/L2

96V dc (460V Se rie s)

~

 

 

 

 

 

 

 

 

 

T /L3

 

 

 

3

EPS/+

1-phase UP S or battery

 

 

 

 

 

Specific ations for

 

 

 

EPS/-

1-phase UP S and battery

 

 

250VDC (for 230V series)

 

 

500VDC (for 460V series)

 

MI1~8

 

 

 

 

To input emergency power

C OM

 

 

Timing diagram of M.C. (magnetic contac t or)

1

2

3

Before inputting emer gency power,

magneti c c ontactor 1

and

3

are ON and

magneti c c ontactor 2

should be O FF.

Magneti c c ontactor 3

should be O N

after magnetic contac tor 1

is ON.

Before removing battery and turn

magneti c c ontactor 2

to be O N,

magneti c c ontactor 1

and

3

should be

OFF.

 

 

 

DC voltage

 

low voltage level

 

battery voltage

 

free

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

run

 

 

 

default EPS operation

motor speed

 

 

 

 

 

mechanical brakefrequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

error output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

electromagnetic

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

about 1 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EPS detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

MI-COM=43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

electromagnetic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

drive ready

 

 

 

 

 

 

 

 

 

 

 

 

 

MO-COM=9

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

about 2 sec.

CAUTION!

1.The wiring of main circuit and control circuit should be separated to prevent erroneous actions.

2.Please use shield wire for the control wiring and not to expose the peeled-off net in front of the terminal.

3.Please use the shield wire or tube for the power wiring and ground the two ends of the shield wire or tube.

4.Damaged insulation of wiring may cause personal injury or damage to circuits/equipment if it comes in contact with high voltage.

2-4

Revision Nov. 2008, VLE1, SW V1.03

Page 29
Image 29
Delta Electronics VFD-VL manual DC voltage Low voltage level Battery voltage, Run, Valve, About 2 sec