Delta Electronics VFD-VL manual 06-00, 06-01, 06-02

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 117
Image 117

Chapter 4 Parameters

Group 6 Protection Parameters

 

 

 

 

 

06-00

Low Voltage Level

 

Unit: 0.1

Control

VF

VFPG SVC

FOCPG TQCPG FOCPM

 

mode

 

 

 

 

 

Settings

230V series

160.0~220.0Vdc

Factory Setting: 180.0

 

 

460V series

320.0~440.0Vdc

Factory Setting: 360.0

 

 

 

 

 

It is used to set the Lv level.

input voltage

 

 

 

 

 

 

 

 

30V(60V)

 

 

 

Pr. 06-00

 

 

 

 

 

 

 

 

 

LV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06-01

Phase-loss Protection

 

 

 

Control

VF

VFPG

 

SVC FOCPG TQCPG FOCPM

 

 

Factory setting: 2

mode

 

 

 

 

 

 

 

 

 

 

Settings

0

 

Warn and keep operation

 

 

 

1Warn and ramp to stop

2Warn and coast to stop

It is used to set the phase-loss treatment. The phase-loss will effect driver’s control characteristic and life.

 

06-02

Over-Current Stall Prevention during Acceleration

Unit: 1

 

 

 

 

 

 

 

Factory setting: 00

 

Control

VF

VFPG SVC

 

mode

 

 

 

 

 

Settings

00~250% (00: disable)

 

 

 

 

 

 

During acceleration, the AC drive output current may increase abruptly and exceed the value specified by Pr.06-02 due to rapid acceleration or excessive load on the motor. When this function is enabled, the AC drive will stop accelerating and keep the output frequency constant until the current drops below the maximum value.

4-62

Revision Nov. 2008, VLE1, SW V1.03

Page 117
Image 117
Delta Electronics VFD-VL manual 06-00, 06-01, 06-02