Chapter 4 Parameters

This parameter is torque command source and the torque command is in Pr.07-12.

07-14

Maximum Torque Command

Unit: 1

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

Factory Setting: 100

mode

 

 

 

 

Settings

0 to 500%

 

 

This parameter is for the max. torque command (motor rated torque is 100%).

 

 

 

07-15

Filter Time of Torque Command

Unit: 0.001

Control

TQCPG

 

Factory Setting: 0.000

mode

 

 

 

 

Settings

0.000 to 1.000 sec

 

When the setting is too long, the control will be stable but the control response will be delay. When the setting is too short, the response will be quickly but the control maybe unstable. User can adjust the setting by the control and response situation.

07-16Speed Limit Selection

Control TQCPG

 

 

Factory Setting: 0

mode

 

 

 

Settings

0

By Pr.07-17 and Pr.07-18

 

 

1

Frequency command source (Pr.00-14)

 

 

 

torque

torque

torque

 

frequency

07-18 07-17

Pr.07-16=0 Running/opposite running direction are

limited by Pr.07-17 and Pr.07-18.

frequency

07-18

07-16=1

When it is forward running, running direction is limited by Pr.00-14

opposite running direction is limited by Pr.07-18.

frequency

00-14

07-16=1

When it is reverse running, running direction is limited by Pr.07-17

opposite running direction is limited by Pr.00-14.

07-17

Torque Mode+Speed Limit

Unit: 1

07-18

Torque Mode-Speed Limit

Unit: 1

Control

TQCPG

 

Factory Setting: 10

mode

 

 

 

 

Settings

0 to 120%

 

 

 

 

 

These parameters are used in the torque mode to limit the running direction and opposite direction. (Pr.01-00 max. output frequency=100%)

4-78

Revision Nov. 2008, VLE1, SW V1.03

Page 133