Schneider Electric 400 TAC Xenta 411/412 Digital Input module, Terminals 411, 412 and Indicators

Models: 400

1 36
Download 36 pages 23.01 Kb
Page 15
Image 15

TAC Xenta 400 I/O modules

3 Technical description

 

 

3.2 The TAC Xenta 411/412 Digital Input module

The modules have ten digital inputs and these inputs can also be used as pulse counters.

In addition, the TAC Xenta 412 is equipped with LED status indicators, one for each digital input. The LED colors, red or green, are individually selectable, by setting switches under the front cover.

Terminals (411, 412) and Indicators (412)

24 V AC/DC Comm - Komm.

 

 

 

}

}

 

 

 

 

 

 

 

~

0

 

 

 

 

 

 

 

 

 

G G0 C1C2 X1 M X2 X3 M X4

 

 

1

2

3

4

5

6

7

8

9 10

DI

10 DI Indicators:

red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 3 4 5 6 7 8 9 10

green

TAC Xenta 412

11 12 13 14 15 16 17 18 19 20

X5 M X6 X7 M X8 X9 M X10

TAC Xenta 411/412 terminals and TAC Xenta 412 DI indicators

 

Type

No.

TAC Menta Block type

Terminal ref.

Indicators (412)

 

 

 

 

 

 

 

Digital input

10

DI - Digital input or

X1 - X10

red or green

 

 

 

CNT - Pulse counter

X1 - X10

red or green

 

 

 

 

 

 

Technical data TAC Xenta 411 and 412

Digital inputs (X1–X10):

 

 

Quantity

10

Voltage across open contact

..............................................

33 V DC

Current through closed contact

4 mA

Pulse input duration (TAC Menta CNT block)

min. 20 ms

LED digital input status indicators (TAC Xenta 412 only):

 

Quantity

10

Color

red or green, selectable via DIP switch

TAC AB, 2003-07-01

0-004-7771-2 (GB), 15 (36)

Page 15
Image 15
Schneider Electric 400 manual TAC Xenta 411/412 Digital Input module, Terminals 411, 412 and Indicators