TAC AB, 2003-07-01 0-004-7771-2 (GB), 29 (36)

TAC Xenta 400 I/O modules 4 Installation

If a shielded communication cable is used, the shield must be groundedat one point only.Redundant wires (second pair of Siemens J-Y(st)Y) are cut at theend of the shield.

Connecting the communication cable

TAC Xenta 1
C1 C2
C1 C2
C1 C2
C1 C2
TAC Xenta 1
TAC Xenta 2 TAC Xenta 2
470 k
¼ W
Shield is grounded
at one point only
Terminals for
incoming cables
Terminals for
incoming cables
Separate
junction
Communication cable,
unshielded
Communication cable,
shielded