4
3
A
1
2
5
C
B
PC/-PA/+
PC/-
PA/+
Part Length in mm (inches)
A Cable jacket 130 (5.2)
B Length of shield connection 60 (2.5)
C Stripping length 6 (0.25)
Diameter ring-type cable lug /
fork-type cable lug
For M5 screw
(1) Strip the cable jacket, length A.
(2) Slide back the shield braiding. Open the shield braiding and
twist it to form a shield connection wire.
(3) Shorten the twisted shield connection wire to length B and insu-
late the shield braiding with heat shrink tube.
Crimp the crimp contacts to the two stripped conductors. The strip-
ping length is C. See chapter "6.1 DC bus accessories", page 55
for information on the crimping tool.
(4) Crimp a fork-type cable lug to the shield connection wire.
Push the crimp contacts into the connector housing. Polarity: the
red wire is PA/+, the black wire is PC/-.
(5) Secure the shield with heat shrink tube.
LXM32 4 Installation
Common DC bus 43
MNA01M001EN, V1.01, 08.2014