NME454, 654 & FME504, 804
SERVICE DIAGNOSIS
Symptom | Possible Cause | Probable Correction |
No ice is made, nothing operates | Unit off due to no power | Restore Power |
|
|
|
| Unit off due to master switch in OFF | Switch master switch to ON. |
| position. |
|
|
|
|
| Unit off due to low water level. | Check water supply, filter, strainer, |
|
| float valve. Correct water supply. |
|
|
|
| Unit off due to ice level sensors | Check/clean ice level sensors. |
|
| |
|
|
|
| Unit off due to scale on water level | Clean water level sensor. |
| sensor. |
|
|
|
|
| Unit off due to high pressure control | Check for water interruption (water |
| open. | cooled) or fan motor failure (air cool). |
|
|
|
| Auger motor hums but does not turn. | Auger can’t turn. Circuit board has not |
|
| yet shut unit down. |
|
|
|
| Unit is shut down | Circuit board has shut ice machine |
|
| down due to high auger motor amp |
|
| draw. Check for cause of high amp |
|
| draw, including bearings, gearmotor |
|
| condition and scale on auger and in |
|
| evaporator. |
|
|
|
| Low pressure control open | Auger not turning due to: motor |
|
| failure; auger relay failure on circuit |
|
| board; or gears stripped. Check drive |
|
| train. |
|
|
|
|
| TXV restricted or not metering. Check |
|
| bulb temperature. |
|
|
|
|
| Lack of refrigerant. Check for leak. |
|
|
|
|
| Check for a restricted system |
|
|
|
| No power to circuit board. | Check harness |
|
|
|
|
| Hi or low pressure cut outs open |
|
|
|
| Circuit Board gear motor relay will not | Check, replace board |
| close |
|
|
|
|
| Water level or ice level sensor failed. | Check, replace sensor |
|
|
|
No ice, auger motor is turning | Compressor contactor coil is open | Check/replace contactor |
|
|
|
| Compressor will not start | Check start capacitor. |
|
|
|
|
| Check start relay |
|
|
|
|
| Check compressor windings |
|
|
|
| Circuit board compressor relay will | Check, replace board |
| not close. |
|
|
|
|
Unit makes ice, but very slowly. | High discharge pressure because of a | Clean the air filter and condenser. |
| dirty condenser |
|
|
|
|
| Low capacity because the auger and | Clean the water system |
| evaporator are coated with mineral |
|
| scale |
|
|
|
|
| Low suction pressure due to low | Locate leak. Recover refrigerant, |
| refrigerant charge | repair leak, replace dryer, evacuate |
|
| and weigh in the nameplate charge |
|
|
|
|
|
|
January 2007