QuickSpecs

HP ProLiant BL20p p-Class Server Blade

Technical Specifications

Operating and

Dimensions

Height

5.25 in (13.34 cm)

5.25 in (13.34 cm)

Performance

 

Width

17.60 in (44.7 cm)

17.60 in (44.7 cm)

Specifications for

 

Depth

27.15 in (68.96 cm)

27.15 in (68.96 cm)

Power Enclosures

 

Weights

No hot-plug power

47.5 lb (21.55 kg)

47.5 lb (21.55 kg)

(International)

 

 

supplies

 

 

 

 

all hot-plug power

99.5 lb (45.13 kg)

125.5 lb (56.93 kg)

 

 

supplies

 

 

 

Input requirements

Rated input voltage

200 VAC to 240 VAC

6.25 A at -48 VDC

 

 

 

 

200 VAC to 240 VAC

 

 

 

 

line to neutral

 

 

Rated input Frequency

50 Hz to 60 Hz

50 Hz to 60 Hz

 

 

Rated input current

24A

20A per phase

 

 

Rated input power

5760 W

10,552 W

 

 

Powercord

1 IEC 309 3-pin, 32A

1 IEC 309 5-pin, 32A

 

 

 

per side

per side

 

Output Voltage

Related output voltage

-48.8 VDC to -54 VDC

-48.8 VDC to -54 VDC

 

Specifications

Related output current

99A

180A

 

 

Related output power

4798 W

8790 W

 

 

Nominal power

4598 W at 208 VAC

8790 W at 230 VAC L-

 

 

 

 

N

 

Ambient Temperature

Operating

50° to 95° F

50° to 95° F

 

Range

 

(10° to 35° C)

(10° to 35° C)

 

 

Non-operating

-22° to 140° F

-22° to 140° F

 

 

 

(-30° to 60° C)

(-30° to 60° C)

 

Relative Humidity

Operating

20% to 80%

20% to 80%

 

(non-condensing)

Non-operating

5% to 95%

5% to 95%

 

Maximum Wet Bulb

Operating

82.4° F (28° C)

82.4° F (28° C)

 

Temperature

Non-operating

101.7° F (38.7° C)

101.7° F (38.7° C)

NOTE: Operating temperature has an altitude derating of 34° F per 1,000 ft (1° C per 304.8 m). No direct sunlight. Upper operating limit is 10,000 ft or 70Kpa (3,048 m or 10.1 psia). Upper non- operating limit is 30,000 ft or 30.3 KPa (9,144 m or 4.4 psia). Storage maximum humidity of 95% is based on a maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.

Operating and

 

Power Bus Box

Mini Bus Bar

Scalable Bus Bar

Performance

Power enclosure or

1

1

2

Specifications for

facility DC supported

 

 

 

Power Distribution

(3U each)

 

 

 

Devices

Server blade

1

3

6

 

 

enclosures

 

 

 

 

Total rack height of

9U

21U

36U

 

supported enclosures

 

 

 

 

Dimensions

 

 

 

 

Height

5.1 in (12.95 cm)

19.45 in (49.40 cm)

48.57 in (123.37 cm)

 

Width

3.6 in (9.14 cm) each

19.74 in (50.14 cm)

19.74 in (50.14 cm)

 

Depth

3.25 in (8.26 cm)

2.2 in (5.59 cm)

2.2 in (5.59 cm)

 

Weight

3.62 lb (1.64 kg )

13.2 lb (5.9 kg)

26 lb (11.79 kg)

 

Rated operating

-43.2 VDC to -54 VDC

43.2 VDC to -54 VDC

-43.2 VDC to -54 VDC

 

voltage

 

 

 

DA - 11411 Worldwide QuickSpecs — Version 24 — 9.24.2004

Page 32

Page 32
Image 32
Server Technology BL20P manual Power Enclosures Weights, Range, Supported enclosures Dimensions, Rated operating, Voltage