Chapter 3: Operations
Modes of Operation
The Sentry
•Normal
Infeed A provides power to branches A1 & A2 and Infeed B provides power to branches B1 & B2. Each infeed is monitored individually for voltage and current.
•Input Failure
The equipment powered by the failed input is transferred to the remaining input. The input current LED display of the failed input will be blank and the remaining display will report the total current load for the unit.
•Recovery from Input Failure
When voltage is restored to the failed input and remains within ±7% of nominal for 2 seconds, the equipment normally supported by that input is transferred back returning the Sentry to a ‘Normal’ mode with the input current LED displays reporting the total current load for each respective infeed.
•Brownout/Over-Voltage
When an input’s voltage varies from its nominal by ±13% or more, the equipment powered by that input is transferred to the remaining input. The input current LED display of the input in the
Nominal Voltage* | Brownout | Recovery Voltage | ||
100V | 87.0V | 93.0V | 107.0V | 113.0V |
110V | 95.7V | 102.3V | 117.7V | 124.3V |
115V | 100.0V | 106.9V | 123.0V | 129.9V |
120V | 104.4V | 111.6V | 128.4V | 135.6V |
208V | 181.0V | 193.4V | 222.6V | 235.0V |
220V | 191.4V | 204.6V | 235.4V | 248.6V |
230V | 200.1V | 213.9V | 246.1V | 259.9V |
240V | 208.8V | 223.2V | 256.8V | 271.2V |
*Nominal operating voltage is configured by the Voltage Selector Switch.
•Recovery from Brownout/Over-Voltage
When the input’s voltage returns to and remains within ±7% of nominal for 2 seconds, the equipment normally supported by that input is transferred back returning the Sentry to a ‘Normal’ mode input current LED displays reporting the total current load for each respective infeed.
•Critical Brownout
A critical brownout is when an input’s voltage drops below its nominal by
•When an input is already in a
•When an input has already failed AND the remaining input experiences a critical brownout, ALL outlets will turn off.
•Recovery from Critical Brownout
When the input’s voltage returns to and remains within ±7% of nominal for 2 seconds, the equipment normally supported by that input is transferred back.
8 • Operations | |