SharkRack Enclosure Installation Guide

Symbols in Text

WARNING: Text set off in this manner indicates that failure to follow directions in the warning could result in bodily harm or loss of life.

CAUTION: Text set off in this manner indicates that failure to follow directions could result in damage to equipment or loss of information.

Note: Text set off in this manner presents commentary, sidelights, or interesting points of information.

Important Safety Notes For Installation

Note:

The information contained in this document is subject to change without notice.

SharkRack makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose.

SharkRack shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material.

SharkRack assumes no responsibility for the use or reliability of the software or hardware installed into a SharkRack cabinet.

Pictures in this manual represent a typical configuration. Your actual configuration may vary.

WARNING:

Always install a stabilizing/anti-tip device such as Floor Mounting Brackets or a Retractable Tip Guard.

Always install the UPS (uninterruptible power supply) in the bottom of the rack. Always install the heaviest equipment in the bottom of the rack.

Always install servers and power devices in the rack from the bottom to the top. Do not extend more than one sliding device at a time.

The center of gravity for an extended unit cannot exceed 16 inches from the face of the cabinet. If an extended device exceeds this distance, the configured cabinet might be unstable.

The maximum allowable weight for devices on slides is dependant upon the specific slide. Do not install sliding devices exceeding maximum allowed weight.

ID-00210-000

REV D, ECO2773