Siemens CE1U2353en01a DHW storage tank, Release, 5010, Charging, Once / day, Several times / day

Models: CE1U2353en01a

1 26
Download 26 pages 40.82 Kb
Page 19
Image 19
DHW storage tank

 

 

@

 

 

 

 

 

2.6

DHW storage tank

Release

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line no.

 

Operating line

 

5010

 

Charging

 

 

 

 

Once / day

 

 

 

 

Several times / day

 

Charging

Selection of charging “Once/day“ or “Several times/day” is active only if DHW release is

 

set according to the time programs of the heating circuits.

 

Once / day

 

Release of DHW charging is given 2.5 hours before the first heat request fom the

 

heating circuit is received. Then, the reduced DHW setpoint applies for the whole day.

 

 

 

 

 

 

TimeHeizprogramm

 

OnceEinmalperproday Tag

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DHWTWWrelease-Freigabe

 

 

 

 

 

 

 

 

2.5h

 

 

 

 

In the case of continuous heating (with no setback periods), release of DHW charging

 

is given at 0:00. The same rule also applies if the first request for heat from the heating

 

circuit is received before 02:30. If a request for heat is delivered at midnight, DHW

 

charging is released after the first setback period, but no earlier than 2.5 hours before

 

midnight.

TimeHeizprogramm

DHWTWWrelease-Freigabe

Day 1

Tag 1

2.5h

Day 2

Tag 2

0:00

2.5h

24:00

2.5h

TagDay 33 DayTag44

22:00

2.5h

Several times / day

When selecting “Several times/day“, release of DHW charging is put forward in time by 1 hour against the periods of time the heating circuit calls for heat, and is then maintained during these periods of time.

TimeHeizprogramm

DHWTWWrelease-Freigabe

1h

1h

MehSevermalstimesproperTag

day

Charging control

 

Line no.

 

Operating line

 

 

 

5024

 

Switching diff

 

 

Switching diff

If the DHW temperature is lower than the current setpoint minus the switching

 

differential set here, DHW charging will be started.

 

 

 

DHW charging will be terminated when the temperature reaches the current setpoint.

 

 

 

 

19/26

 

 

 

 

 

 

Siemens Schweiz AG

User Manual OEM

 

CE1U2353en01a

HVAC Products

The settings in detail

22. November 2006

Page 19
Image 19
Siemens CE1U2353en01a DHW storage tank, Release, 5010, Once / day, Several times / day, Charging control, 5024