| 2.9 | Error | |
History 1...10 |
|
|
|
|
|
|
|
| Line no. |
| Operating line |
| 6820 |
| Reset history |
|
|
| No |
|
|
| Yes |
Reset history | The error history with the last 10 errors will be deleted. |
Heating circuit 1, heating circuit 2, heating circuit P
Room temperature 1 / 2 / P model
2.10 Diagnostics consumers
Line no. | Operating line |
8742 | Room temp 1 model |
8772 | Room temp 2 model |
8802 | Room temp P model |
The room model calculates a fictive room temperature for rooms that have no room temperature sensor. The value calculated for each heating circuit is indicated on these operating lines.
This allows boost heating, quick setback and optimum start and stop control to be implemented with no need for using a room temperature sensor.
The calculation takes into account the attenuated outside temperature (operating line 8703), the room model gradient (operating line 6112) for switching to a higher setpoint, and the building’s time constant (operating line 6110) for switching to a lower setpoint.
|
| 23/26 |
|
|
|
Siemens Schweiz AG | User Manual OEM | CE1U2353en01a |
HVAC Products | The settings in detail | 22. November 2006 |