1.2Fixed Application Problems

Maintenance Info MI291a: Guarto MP3 SR2

1.2Fixed Application Problems

The current RTC chip is not available anymore. So, a new pin compatible device with a new chip was produced in cooperation for Guarto and AlgoRex. This re- quires the use of a new RTC driver, which supports the current chip as well as the new device.

Therefore, a new HW version is provided too, where the current RTC chip is re- moved from the board and a socket is mounted instead, so that the piggy-back de- vice with the new RTC chip can be inserted.

1.3Fixed Tool Problems

For the mentioned SR1 of MP3 an improved SWE6 tool V5.0a was provided.

The following problems were fixed:

zThe delay of remote transmission for 'Security-jeopardizing fault' and 'Major fault' was not visible and configurable anymore

(new range for each remote transmission type 10..1800s)

zGeneration of CNAP profile adjusted that a data import of the management sys- tem doesn't stop anymore because of a section without zone

zListing of configuration data (for sections) contained also the section number and not only the numbers of the linked zones

Installation (Update V5.0):

Uninstall SWE6 MP3 V5.0

Install SWE6 MP3 V5.0

Î When this message appears: click No