Slant/Fin LDZO Series dimensions ASME Required Options, Ratings, Modular Boiler Submittal Data

Models: LDZO Series

1 2
Download 2 pages 8.4 Kb
Page 1
Image 1
 ® Modular Boiler Submittal Data

LDZO SERIES—Oil-Fired/SteamASME Required OptionsRatingsManual background ® Modular Boiler Submittal Data

LDZO SERIES—Oil-Fired/Steam

A Caravan modular boiler system consists of two or more compact cast-iron boilers that offer significant advantages in terms of installed cost, efficiency and reliability. Caravan systems are based on step-firing just enough modules to meet space heating demands. LDZO systems are available in 602,000 to multi-million Btuh gross input. For additional information, see Caravan Engineering Manual, pub. C-30.

Standard Equipment

 

 

 

 

One per module unless otherwise noted

 

 

 

Pre-assembled cast-iron heat exchanger

 

 

 

with insulated jacket

 

 

 

Flame retention oil burner, with nozzle;

 

 

 

cadmium sulfide flame detector

 

 

 

Primary burner control

 

 

 

System pressure gauge and siphon

 

 

 

(unmounted, one per system)

 

 

 

Module pressure gauge and siphon

 

 

 

(unmounted)

Module drain cock

ASME Required Options

 

Module pressure relief valve (ASME)

(unmounted)

67 Low water cut off (one per module)

(unmounted) 15 PSI.

Water level sight glass

PA404A Pressure control (one per module)

Draft regulator (unmounted)

(unmounted)

67M Low water cut off (one per system)

Flue brush

 

L4079B Manual reset pressure control

 

 

 

(one per system)

Ratings

Oil Caravan ratings and dimensions/steam models — LDZO Series

 

 

 

 

Ratings for No. 2 Oil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I=B=R

 

 

 

Boiler

 

Recom-

 

 

 

 

 

 

 

 

 

 

 

 

No. of

Burner

 

Gross

Comb.

 

Net

 

 

Water

Weight

mended

 

Heating

Capacity

Input

Output

 

Output

Sq.Ft

Horse-

Content

with

Header

Model No.

Modules

(GPH)*

(MBH)

MBH

Efficiency

 

MBH†

Steam‡

power

(gal)

Water

Size

LDZO-600-2-5

2

4.3

602

500

85.90

 

375

1563

14.9

21.4

1426

3"

LDZO-750-2-6

2

5.2

728

596

85.80

 

447

1863

17.8

25.2

1630

3"

LDZO-850-2-7

2

6.0

840

684

85.50

 

513

2138

20.4

29.0

1838

3"

LDZO-900-3-5

3

6.4

896

750

85.90

 

563

2345

22.4

32.1

2139

3"

LDZO-1100-3-6

3

7.8

1092

894

85.80

 

671

2796

26.7

37.8

2445

5"

LDZO-1300-3-7

3

9.0

1260

1026

85.50

 

770

3208

30.6

43.5

2756

5"

LDZO-1700-4-7

4

12.0

1680

1368

85.50

 

1035

4313

40.9

58.0

3675

6"

LDZO-2100-5-7

5

15.0

2100

1710

85.50

 

1319

5496

51.1

72.5

4594

6"

* Light oil, 140,000 Btu. per gallon.

Net ratings are based on piping and pick-up allowance of 1.33. Slant/Fin should be consulted before selecting a boiler for installation having unusual piping and/or pick-up requirements. For higher elevations, input may need to be reduced

‡ Based on 240 Btuh per square foot E.D.R. at 215˚F average steam temperature.

Modules in excess of 5 are piped in parallel in two or more banks.

Page 1
Image 1
Slant/Fin LDZO Series dimensions ASME Required Options, Ratings, Modular Boiler Submittal Data