Hardwiring
Wiring must be performed by a qualified electrician.
1.Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring.
2.Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.
3.Remove the access panel (see B).
4.Remove circular knockouts.
5.Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical codes. (See tables and graphics.)
6.Use appropriate
XLT, XLJ, AND XLTW MODELS
Input Connection |
|
|
|
|
|
|
|
|
|
|
|
|
| Output Connection (optional) |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Wire to L1, L2, and |
|
| . |
|
|
|
|
|
|
|
|
| Wire to L1A, L2A, and |
|
|
| . |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
System |
|
| Wiring |
|
|
| Voltage | Current |
| External Input Circuit |
| Wire Size | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Full Load |
| Breaker (typical) |
| (typical) | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| (Nominal) |
|
|
|
|
|
|
|
|
| ||
SURT8000XLJ, |
|
| Input & |
|
|
| 200/208/220/240 V | 40 A |
|
| 50 A / |
| 10mm2 * | ||||||||||||
SURT8000XLT, |
|
| Output |
|
|
|
|
|
|
|
|
|
|
| for Input Wiring only |
| #8 AWG | ||||||||
SURT8000XLTW |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
SURT10000XLJ, |
|
| Input & |
|
|
| 200/208/220/240 V |
| 60 A or 63 A / |
| 16mm2 * | ||||||||||||||
SURT10000XLT, |
|
| Output |
|
|
|
|
|
|
|
| for Input Wiring only |
| #6 AWG | |||||||||||
SURT10000XLTW |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
XLI MODELS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Input Connections |
|
|
|
|
|
|
|
|
|
|
|
|
| Output Connection (optional) |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
| . |
|
|
|
| Wire to L1A, N1, and |
|
|
| . |
|
| ||||||||||||
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
| . |
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
System |
| Wiring |
| Number |
| Voltage |
| Current |
|
|
| External Input |
| Wire Size | |||||||||||
|
|
|
|
|
|
| of |
|
|
|
| Full Load |
|
|
| Circuit Breaker |
| (typical) | |||||||
|
|
|
|
|
|
| Phases |
|
|
|
| (Nominal) |
|
|
| (typical) |
|
| |||||||
SURT8000XLI |
| Input |
| 1 |
|
|
|
| 220/230/240 V |
| 40 A |
|
|
| 50 A / |
| 10mm2 * | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
| Input |
| 3+ |
|
|
| 380/400/415 V |
| 15 | A / phase when |
|
|
| 50 A / |
| 10mm2 * | ||||||||
|
|
|
|
|
|
| Neutral |
|
|
|
| online |
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 40 | A on L1 in bypass |
|
|
| ||||||
|
| Output |
| 1 |
|
|
|
| 220/230/240 V |
| 40 | A |
|
|
| (not required) |
| 10mm2 * | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
SURT10000XLI |
| Input |
| 1 |
|
|
|
| 220/230/240 V |
| 50 A |
|
|
| 63 A / |
| 16mm2 * | ||||||||
|
| Input |
| 3+ |
|
|
| 380/400/415 V |
| 18 | A / phase when |
|
|
| 63 A / |
| 16mm2 * | ||||||||
|
|
|
|
|
|
| Neutral |
|
|
|
| online |
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 50 | A on L1 in bypass |
|
|
| ||||||
|
| Output |
| 1 |
|
|
|
| 220/230/240 V |
| 50 | A |
|
|
| (not required) |
| 16mm2 * |
*Recommended wire sizes are typical. Actual wire size must comply with required ampacity and local and national electrical codes.