Hardwiring

Hardwiring

Wiring must be performed by a qualified electrician.

1.Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring.

2.Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.

3.Remove the access panel (see B).

4.Remove circular knockouts.

5.Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical codes. (See tables and graphics.)

6.Use appropriate strain-relief on the hardwired input and output power cables.

XLT, XLJ, AND XLTW MODELS

Input Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Connection (optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wire to L1, L2, and

 

 

.

 

 

 

 

 

 

 

 

 

Wire to L1A, L2A, and

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

 

Wiring

 

 

 

Voltage

Current

 

External Input Circuit

 

Wire Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load

 

Breaker (typical)

 

(typical)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Nominal)

 

 

 

 

 

 

 

 

 

SURT8000XLJ,

 

 

Input &

 

 

 

200/208/220/240 V

40 A

 

 

50 A / 2-pole

 

10mm2 *

SURT8000XLT,

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

for Input Wiring only

 

#8 AWG

SURT8000XLTW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SURT10000XLJ,

 

 

Input &

 

 

 

200/208/220/240 V

XLJ-50 A

 

60 A or 63 A / 2-pole

 

16mm2 *

SURT10000XLT,

 

 

Output

 

 

 

 

 

 

 

XLT-48 A

 

for Input Wiring only

 

#6 AWG

SURT10000XLTW

 

 

 

 

 

 

 

 

 

 

 

 

XLTW-48 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XLI MODELS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Connection (optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-Phase: Wire to L1, N, and

 

 

.

 

 

 

 

Wire to L1A, N1, and

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three-Phase: Wire to L1, L2, L3, N, and

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

Wiring

 

Number

 

Voltage

 

Current

 

 

 

External Input

 

Wire Size

 

 

 

 

 

 

 

of

 

 

 

 

Full Load

 

 

 

Circuit Breaker

 

(typical)

 

 

 

 

 

 

 

Phases

 

 

 

 

(Nominal)

 

 

 

(typical)

 

 

SURT8000XLI

 

Input

 

1

 

 

 

 

220/230/240 V

 

40 A

 

 

 

50 A / 2-pole

 

10mm2 *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

3+

 

 

 

380/400/415 V

 

15

A / phase when

 

 

 

50 A / 4-pole

 

10mm2 *

 

 

 

 

 

 

 

Neutral

 

 

 

 

online

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

A on L1 in bypass

 

 

 

 

 

Output

 

1

 

 

 

 

220/230/240 V

 

40

A

 

 

 

(not required)

 

10mm2 *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SURT10000XLI

 

Input

 

1

 

 

 

 

220/230/240 V

 

50 A

 

 

 

63 A / 2-pole

 

16mm2 *

 

 

Input

 

3+

 

 

 

380/400/415 V

 

18

A / phase when

 

 

 

63 A / 4-pole

 

16mm2 *

 

 

 

 

 

 

 

Neutral

 

 

 

 

online

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

A on L1 in bypass

 

 

 

 

 

Output

 

1

 

 

 

 

220/230/240 V

 

50

A

 

 

 

(not required)

 

16mm2 *

*Recommended wire sizes are typical. Actual wire size must comply with required ampacity and local and national electrical codes.

2

Page 4
Image 4
Smart Inventions 990-2689E manual Hardwiring, Wiring must be performed by a qualified electrician