SMC Networks D-P5DW specifications Installation and Maintenance Manual, Safety Instructions

Models: D-P5DW

1 1
Download 1 pages 53.69 Kb
Page 1
Image 1
Installation and Maintenance Manual

013A/ENGD-#S-TFI99GB

Installation and Maintenance Manual

Solid State Auto-Switch Series D-P5DW

For future reference, please keep this manual in a safe place

This manual should be read in conjunction with the current product catalogue

Problem

2 wire type (Sink output)

 

 

2 wire type (Source output)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT(+)

 

 

 

 

 

OUT(+)

 

 

 

 

 

 

Load

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

Brown (Red)

 

 

 

Brown (Red)

 

 

 

 

 

source

 

 

 

 

 

 

Switch

 

Switch

 

 

Power

 

 

OUT(-)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT(-)

source

 

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blue (Black)

 

 

 

 

 

Blue (Black)

 

 

Safety Instructions

These safety instructions are intended to prevent a hazardous situa- tion and/or equipment damage. These instructions indicate the level of potential hazard by label of “Caution”, “Warning” or “Danger”. To ensure safety, be sure to observe ISO4414 (Note1), JIS B 8370 (Note2) and other safety practices.

Note 1: ISO 4414: Pneumatic fluid power – Recommendations for the application of equipment to transmission and control systems.

Note 2: JIS B 8370: Pneumatic system axiom.

CAUTION : Operator error could result in injury or equipment damage.

WARNING : Operator error could result in serious injury or loss of life.

DANGER : In extreme conditions, there is a possible result of serious injury or loss of life.

WARNING

1.The compatibility of pneumatic equipment is the respon- sibility of the person who designs the pneumatic system or decides its specifications.

Since the products specified here are used in various operating conditions, their compatibility for the specific pneumatic system must be based on specifications or after analysis and/or tests to meet your specific requirements.

1.Product specification

2.Only trained personnel should operate pneumatically operated machinery and equipment.

Compressed air can be dangerous if an operator is unfamiliar with it. Assembly, handling or repair of pneumatic systems should be performed by trained and experienced operators.

3.Do not service machinery/equipment or attempt to remove component until safety is confirmed.

1)Inspection and maintenance of machinery/equipment should only be performed after confirmation of safe locked-out control positions.

2)When equipment is to be removed, confirm the safety process as mentioned above. Switch off air and electrical supplies and exhaust all residual compressed air in the system.

3)Before machinery/equipment is re-started, ensure all safety measures to prevent sudden movement of cylinders etc. (Bleed air into the system gradually to create back-pressure, i.e. incorporate a soft-start valve).

4.Contact SMC if the product is to be used in any of the following conditions:

1)Conditions and environments beyond the given specifica- tions, or if product is used outdoors.

2)Installations in conjunction with atomic energy, railway, air navigation, vehicles, medical equipment, food and beverage, recreation equipment, emergency stop circuits, press applications, or safety equipment.

3)An application which has the possibility of having negative effects on people, property, or animals, requiring special safety analysis.

CAUTION

Ensure that the air supply system is filtered to 5 micron.

 

 

Condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stay ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(sometimes OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicator

 

 

 

Stay ON

 

 

 

 

 

Stay OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lamp lights

 

 

 

 

 

 

 

(sometimes ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stay

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

 

Indicator

 

 

 

 

 

 

 

Stay OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lamp lights

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Source voltage

 

 

 

 

 

 

 

 

 

 

 

 

2 wires/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or load voltage

 

 

 

 

 

 

 

 

 

 

 

 

3 wires

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

Abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 wires/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 wires

 

 

2 wires

 

 

 

 

 

 

 

 

 

 

2 wires

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 wires

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

wires

 

 

 

 

 

 

Load

spec.

 

 

 

 

 

 

Replace the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load spec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

check 1

 

 

 

 

 

 

switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

check 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

Abnormal

 

 

 

Normal

 

 

Abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

Abnormal

 

 

 

 

Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(output) check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal

 

 

Abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

B

 

 

 

 

 

A

 

C

 

 

 

D

 

E

 

B

 

B

 

A

 

 

A

 

F

D

Load spec. check 1 . . .ON voltage > Load voltage - Internal voltage drop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig 4

Exterior dimensions

D-5DW

Indicator lamp

2 8

4

. .

.

9 8

ø3

 

32

4

6

2-ø3. 5

1

 

5

ø6

 

20

 

Fig 3

Basic wiring (Fig 4)

Lead wire colour in brackets indicates products complying with IEC.

Connection with PLC (sequence controller)

Depending on the PLC input specification, the output design of 3 wire type switches and 2 wire type switches differ. (See below)

ON

OFF

Red Green Red

Operating range

Fig 6

Solid State Auto-Switch Series D-P5DWCAUTION

Welding current

This product has no immunity against high magnetic fields. Do not use in applications where welding takes place using D.C. inverter/rectified source. If using in conjunction with a D.C. welding application remove the switch from the D.C. source and operate it as a standard switch. As a rule of thumb, in this type of application, to prevent malfunction use the scale 10,000A switch which should be at least 30cm away from the source.

Effect of magnetisation/de-magnetisation

In the case of exceeding the 10,000A, although this is very rare, the detecting performance of the switch will deteriorate, due to de-magnetisation (the magnetic field shrinks) of the detecting magnet. Parts around the actuator also become magnetised.

Should any malfunction occur please contact your nearest SMC office

Model number

D-P5DW

 

 

Wiring style

Two wire type, Non-polarity

Application

24V DC Relay, PLC

Source voltage

––

Current consumption

––

Load voltage

DC24V (DC20~28V)

Load current

6~40mA

Internal voltage drop

5V or less

Load spec. check 2 . . .OFF current > Leak current

 

 

A

. . .Switch output parts failure (replace)

D

. . . .Switch failure

B

. . .Correct wiring

E

. . . .Replace cylinder. Detectable magnet field inadequate (No magnet)

C

. . .Replace switch 2 wires R 3 wires

F

. . . .Replace PLC input board or replace switch 2 wire R3 wires

PLC input specification

2 wire connecting type

Sink input

Sink output mode

Source input

Source output mode

 

 

Mounting of switch bracket

 

Each actuator has a specified mounting bracket to mount the switch to the actuator. The type of bracket depends on the following:

for advice.

For future reference, please keep this manual in a safe placeCAUTION

In all cases do not clean with a solvent solution.

When you enquire about the product, please contact the following

SMC Corporation:

 

ENGLAND Phone 01908-563888 TURKEY

Phone 212-2211512

 

Leak current

 

1mA or less at DC24V

 

Operating time

 

40ms or less

 

 

Operating

 

Two colour

 

indicator lamp*1

 

 

 

 

 

 

Magnet field

 

AC16000A

 

proof *2

 

 

 

 

 

 

Proof impact

 

1000m/s2

 

 

Insulation resistance

50M Ω or more at DC500V mega

 

 

Proof voltage

AC1000V for 1 minute (lead wire, between cases)

 

 

Ambient temperature

 

-10~60°C

 

 

Protection structure

IEC529 standard IP67, JISC0920

 

*1 Operating position. . .Red diode lights, Optimum operating position . . . Green diode lights

*2 Applicable adjacent to conductor (0mm)

 

 

 

 

 

 

drop and leak current have a considerable influence on the serial and

 

Installation

 

 

Actuators

 

parallel connection of the 2-wire solid state switch.

 

 

 

 

Fig 1

or Solenoid valve, a built-in surge protection circuit is installed.

If an auto-switch is to be used to generate an inter-lock signal, which requires high reliability, then instigate mechanical protection, or place another switch, double inter-lock style, together. Ensure the correct operation of this Inter-lock frequently.

Ensure, when installing this product, that enough space is available for maintenance to be carried out.

Safety InstructionsCAUTION

Do not subject this product to any form of impact damage.

Do not lift an actuator, fitted with an auto-switch, by the switch lead, as stress may be applied to the inside of the switch.

Ensure auto-switch mounting screw is tightened to the correct torque (see Mounting of switch bracket).

of the switch operating Spec.

Protect the switch from weld spatter and accumulation of iron dust etc.

Maintenance

To avoid incorrect operation periodic maintenance should be carried out.

Check tightness of mounting screw regularly to prevent possible movement of the switch from its set position.

Regularly check condition of the wiring. Repair insulation damage immediately or replace the switch.

If a red LED is showing this indicates that the switch has moved from the set position. Re-adjust the switch until the green LED is showing (this is the optimum position).

CAUTION : Operator error could result in injury or equipment damage.CAUTION

Type of actuator, and tube O.D. Please consult the current

actuator catalogue for details.

When fitting an auto-switch for the first time please ensure that the actuator is fitted with a magnet and that the brackets are correct for the actuator type.

Autoswitch set screw

M3x0.5x10l

ITALY

Phone 02-92711

GERMANY

Phone 6103-402-0

HOLLAND

Phone 020-5318888

FRANCE

Phone 01-64-76-10-00

SWITZERLAND Phone 052-396 31 31

SWEDEN

Phone 08-603 07 00

SPAIN

Phone 945-184100

AUSTRIA

Phone 02262-62-280

 

Phone 902-255255

IRELAND

Phone 01-4501822

GREECE

Phone 01-3426076

DENMARK

Phone 70 25 29 00

FINLAND

Phone 09-68 10 21

NORWAY

Phone 67-12 90 20

BELGIUM

Phone 03-3551464

POLAND

Phone 48-22-6131847

 

 

PORTUGAL

Phone 02-610 8922

1.Product specificationWARNING

To eliminate the possibility of magnetic interference between switch- es, please ensure that, when two or more actuators are used, in parallel, they are kept at least 40mm apart.

Exterior dimensions Mid-stoke position sensing

Exercise caution when attempting to detect the piston at mid-position, without stopping, as the switch detection time may be too short, particularly at relatively high actuator speeds. Detectable max. piston speed can be obtained by the following formula:

V (mm/s) =

Auto switch operating range (mm)

x1000

 

 

Load operating time (ms)

Leak current influence

I.E Voltage generated to the load when the power is turned off.

Voltage generated = Auto-switch leak current x load resistance. If this voltage exceeds the OFF voltage of the load, it is possible that the load may stay ON. In order to match the condition of the controller-input unit and leak current, then auto-switch leak current must be less than input unit OFF current.

Internal voltage drop

Should an internal voltage drop occur, then the load supply voltage will also drop as the switch operates. (Load supply voltage = Source voltage – Internal voltage drop).

When the load supply voltage becomes lower than the switch ON voltage, the load may not operate correctly.

Adjust the auto-switch so that the ON position coincides with the cen- tre of the operating area. If the switch is set to one side or the other of this centre position then inconsistent operation will occur.

Wiring

Do not apply repeated bending or tensile forces to the connecting wiring as this may cause disconnection. Bend radius is approximately R40mm or more.

Connect the load before applying power to the switch, failure to do so may cause excess current to damage the switch.

Ensure wiring is carried out correctly. Not all wiring modes have pro- tection and the switch may be damaged.

Separate signal lines from power/high voltage lines to prevent 'noise'. Ensure all wiring is correctly and fully insulated.

If detection failure occurs i.e. LED remains ON follow the faultfinding chart above (Fig 1).

For applications involving contact with water, elasticity, and welding, contact your nearest SMC Office. (See at the end of this Manual.)

If the hysteresis, between the ON and OFF position of the switch is incorrect please consult SMC.

Hysteresis

Piston moving

 

 

 

ON position

direction

 

 

 

 

 

 

 

 

Fig 5

Appropriate tightening torque

M3 mounting screw correct tightening torque is 0.5~0.7 Nm (5.1~7.1 kgf.cm)S

Setting the switch detection position (Fig 6)

Position the actuator at its stroke end.

Single colour display

Move the auto-switch into the centre of the operating range and ensure that the red LED is ON.

Two colour display

Where possible keep all wiring as short as possible.

WARNING

 

CAUTION

Incorrect load voltage

 

 

Although the switch will operate correctly, even if the load current is

If the 2-wire type solid state auto-switch has a large internal voltage

below the limit of the specification, the indicator light will be

drop, and leakage current is also high, it is possible that the load may

'dimmed'. If the load current falls to 3mA, or lower, the operation may

not operate correctly due to incorrect load spec. Please confirm the fol-

not start.

lowing conditions before operation, and note that the internal voltage

Ensure that, if using a load that can generate a surge voltage ie. Relay

Basic wiring (Fig 4) WARNING

DO NOT USE THIS SWITCH IN AN EXPLOSIVE ATMOSPHERE.

Do not use this switch in high magnetic fields, as this will damage the switch and actuator magnet.

Do not use this switch in water-laden atmospheres, oil or chemical laden atmospheres.

Do not use this switch in conditions where temperatures are outside

Piston moving

 

 

Hysteresis

direction

 

 

 

 

 

 

 

OFF position

 

 

 

 

Fig 2

Move the Auto-switch into the centre of the operating range and ensure that the green LED is ON.

Detecting actuator stroke end

Refer to dimensions A & B in the actuator catalogue.

Page 1
Image 1
SMC Networks specifications Installation and Maintenance Manual, Solid State Auto-Switch Series D-P5DW, Wiring