SECTION 2: BOILER INSTALLATION
STEP 1: LOCATING AND SETTING THE BOILER
➤PROCEDURE A: Check that provisions for combustion air are in accordance with National Fuel Gas Code ANSI
➤ PROCEDURE B: |
|
| FIGURE 2.1 |
|
|
| |
Check minimum | 6" | 6" |
|
clearances to |
| ||
|
|
| |
combustibles are |
|
|
|
proper as shown. Local |
| VENT DAMPER |
|
requirements may |
|
| |
| * TOP |
| |
specify greater |
|
|
|
clearances & must be |
|
|
|
adhered to. |
|
|
|
Boiler shall be install- | 18" | 12" | 12" |
ed such that the gas |
| RECOMMEND |
|
ignition system com- |
| MORE FOR |
|
| ACCESS TO |
| |
ponents are protected |
| VENT DAMPER |
|
| POSITION |
| |
from water (dripping, |
| INDICATOR |
|
|
|
| |
spraying, rain, etc.) |
|
|
|
during appliance oper- |
|
|
|
ation and service. |
|
|
|
|
| * 52" FOR |
|
|
| 58" FOR |
|
WARNING: Never install boiler on combustible flooring without combustible flooring pan or on carpeting as heat damage and/or fire may result.
CAUTION: Locate boiler so horizontal connecting flue pipe is as short as possible. Maximize height of vertical flue connector.
NOTE: Do not loosen tie rods on absorption unit. They accommodate thermal expansion. Loss of boiler structural integrity and water leaks/damage may result.
Step 1 Continued On Next Page
5