SSI
EPS2U Power Supply Design Guide, V2.1
6.6Dynamic Loading
STATUS
Required
The output voltages shall remain within the limits specified in Table 18 for the step loading and within the limits specified in Table 20 for the capacitive loading. The load transient repetition rate shall be tested between 50 Hz and 5 kHz at duty cycles ranging from
Table 20: Transient Load Requirements
Output | ∆ Step Load Size | Load Slew | Capacitive Load |
|
| Rate |
|
+3.3 V | 30% of max load | 0.5 A/µs | 1000 µF |
|
|
|
|
+5 V | 30% of max load | 0.5 A/µs | 1000 µF |
|
|
|
|
12V1+12V2+12V3+12V4 | 65% of max load | 0.5 A/µs | 2200 µF |
|
|
|
|
+5 VSB | 25% of max load | 0.5 A/µs | 1 µF |
|
|
|
|
6.7Capacitive Loading
STATUS
Required
The power supply shall be stable and meet all requirements with the following capacitive loading ranges. Note: Up to 10,000 µF of the +12V capacitive loading may be on the +12V1 output.
Table 21: Capacitve Loading Conditions
Output | MIN | MAX | Units |
+3.3 V | 10 | 12,000 | µF |
|
|
|
|
+5 V | 10 | 12,000 | µF |
|
|
|
|
+12 V | 10 | 11,000 | µF |
|
|
|
|
1 | 350 | µF | |
|
|
|
|
+5 VSB | 1 | 350 | µF |
|
|
|
|
- 20 -