Sterling 882.00440.00 SC6-610.6 Structural Steel Support Requirements, Fiberglass Cooling Towers

Models: 882.00440.00 SC6-610.6

1 25
Download 25 pages 20.01 Kb
Page 11
Image 11
Figure 1: Structural Steel Support Requirements

Figure 1: Structural Steel Support Requirements

 

 

 

Structural steel

 

 

2 X 2 angle

B

 

B

 

 

 

to support

 

 

 

tower basin,

D

 

 

flush with top

 

A

 

 

of structural

 

 

 

 

 

steel rails

 

 

 

C

C

C

C

 

 

TSE50

 

Model

 

 

A

 

 

 

B

 

 

 

C

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number

 

in.

 

cm

 

in.

 

cm

 

in.

cm

 

in.

cm

SF2003

52

 

132.1

50

 

127.0

16

40.6

78

175.3

SF2004

52

 

132.1

50

 

127.0

16

40.6

78

175.3

SF2005

68

 

172.7

67

 

170.2

22

55.9

78

175.3

SF2007

68

 

172.7

67

 

170.2

22

55.9

78

175.3

SF2009

87

 

221.0

85

 

215.9

28

71.1

78

175.3

SF2011

87

 

221.0

85

 

215.9

28

71.1

78

175.3

SF2015

87

 

221.0

85

 

215.9

28

71.1

78

175.3

Note: The illustration in Figure 1 shows structural steel with spacing for two (2) cooling towers. Your installation may vary.

Dimension A – Centerline for fiberglass mounting feet provided with cooling tower. This is so bolt holes can be made to secure the tower to the structural support.

Dimension B & C – Location of basin support steel.

Dimension D – Provides proper distance of 60” between cooling towers and distance between cooling tower and the wall of a building.

Fiberglass Cooling Towers

Chapter 3: Installation

Page 11 of 25

Page 11
Image 11
Sterling 882.00440.00 SC6-610.6 Structural Steel Support Requirements, Fiberglass Cooling Towers, Installation, Page 11 of