GP Series Portable Chillers Chapter 7: Appendix 50 of 64
7-6 Typical Ductwork for Air-Cooled Chillers
Fan 60 Hz Discharge
air volume 50 Hz Discharge
air volume
Model HP kW CFM m3/min CFM m3/min
GPAC-20 0.5 0.4 4230 120 3525 100
GPAC-30 1.0 0.7 6343 180 5286 150
GPAC-40 1.0 0.7 8458 240 7048 200
GPAC-50 2.0 1.5 12687 360 10573 300
When locating your air-cooled portable chiller and designing its ductwork, note any potential high
temperature conditions when discharging into your building and any negative pressures with the building
when discharging air outside.
Notes: Customer use of ductwork requires the high pressure fan option. Allow 30” (77 cm) minimum
clearance around the chiller footprint to facilitate free passage of cooling air and service accessibility
Size the ductwork for maximum capacity Support ductwork from the building structure, not off of the
chiller Back draft damper to outside must be closed at all times when fan/blower is not operating