3-7 Condenser Considerations

Water-Cooled Chiller Condensers

Water-cooled portable chillers can use city water or tower water as a cooling medium. Make sure that all external piping and connections supplying and discharging water to and from the condenser are full size.

You’ll make two connections to the water-cooled condenser:

Condenser Water In. The condenser water supply, labeled “Condenser Water In”, is located at the rear of the chiller. It is the inlet for city or tower water.

Make sure that water is supplied at a maximum temperature of 85ºF (29ºC) and a minimum pressure of 25 psi.

The water-regulating valve is set at the factory. Only a qualified refrigeration technician should adjust it.

Normal R-22 refrigerant condensing pressure is 210 psi, with 85ºF (27ºC) water at 25 psi entering condenser water pressure

Condenser Water Out. Condenser water return, labeled “Condenser Water Out”, is located at the rear of the chiller. It is the outlet for water after it has passed through the condenser.

It is connected to the tower water return line or to a sewer or other approved discharge receiver. A water-regulating valve is a standard feature in the condenser water return line.

Air-Cooled Chiller Condensers

Air-cooled chillers use the surrounding air to cool the condenser. Install the chiller in an area where there is free passage of air for condensing and provisions for removal of heated air from the area. Do not locate air-cooled chillers in locations where steam, hot air, or fume exhausts can be drawn into the chiller. A typical ductwork diagram is located on page 63 in the Appendix of this manual.

Caution! Clean air-cooled condensers and filters frequently. Failure to do so results in reduced capacity, increased operating costs, and possible failure of the equipment. Cleaning instructions can be found on page 38 in the Maintenance chapter of this manual

Normal maximum refrigerant condensing pressure with 95ºF (35ºC) air entering the condenser is 260 psi.

Condensing Air Temperature. Our air-cooled portable chillers are designed to operate at a minimum condenser entering air temperature of approximately 60ºF (15.5ºC). Operation of the equipment at a lower condenser entering air temperature can cause the chiller to lose capacity. For entering air temperatures below 60ºF, an optional fan motor speed control is available. We recommend maintaining a minimum 60ºF ambient temperature.

2-40 HP Portable Chillers

Chapter 3: Installation

19 of 70

Page 19
Image 19
Sterling A0554831 manual Condenser Considerations, Water-Cooled Chiller Condensers, Air-Cooled Chiller Condensers

A0554831 specifications

The Sterling A0554831 is a versatile and powerful tool designed for a range of applications, particularly in the industrial and construction sectors. Known for its robust construction and reliability, it has gained popularity among professionals and DIY enthusiasts alike.

One of the main features of the Sterling A0554831 is its durable build quality, which is designed to withstand harsh working conditions. The device typically features a high-strength casing that protects it from dust, moisture, and impact, ensuring longevity even in the most demanding environments. Its ergonomic design allows for comfortable handling, minimizing user fatigue during extended use.

In terms of performance, the Sterling A0554831 is equipped with advanced technologies that enhance its efficiency and functionality. The device is powered by a high-torque motor, delivering impressive power that enables it to tackle heavy-duty tasks with ease. The precision-engineered components ensure consistent performance, making it ideal for tasks that require accuracy and reliability.

Another significant characteristic of the Sterling A0554831 is its versatility. It typically comes with multiple settings and modes, allowing users to adjust the tool according to the specific requirements of their project. Whether drilling, cutting, or fastening, the tool can accommodate various tasks, making it a valuable addition to any toolkit.

Safety features are also a priority with the Sterling A0554831. Many models are equipped with overload protection and safety switches that prevent accidental activation, safeguarding the user during operation. Additionally, some variants may include LED indicators that provide real-time information about battery life or operational status, enhancing overall user experience.

In conclusion, the Sterling A0554831 stands out in the market for its combination of durability, performance, and versatility. With advanced technologies that cater to a wide range of applications and a design focused on user comfort and safety, this tool is an excellent choice for professionals looking for dependable and effective solutions in their work. Whether you are a seasoned professional or a casual DIYer, the Sterling A0554831 is well-equipped to handle your needs with ease and efficiency.