STOW G-2.9R — INITIAL START-UP ENGINE/OPERATION
6.If the engine has started, slowly return the choke lever (Figure 12 ) to the “OPEN” position. If the engine has not started repeat steps 1 through 5.
7.Beforethegeneratorisplacedintooperation,runtheengine for
8.Refer to the AC voltmeter (Figure 16) on the control box. The voltage indicated on the voltmeter should be 120 VAC with no load applied.
Stopping The Engine
Normal Shutdown
1.Place the main circuit breaker (Figure 10) in the OFF position.
2.Remove the load from the generator, and let the engine run at idle for
3.Place the operation switch (Figure 17) in the OFF position S/N 5497956 and below).
Figure 19. Operation Switch (OFF)
Figure 16. AC Voltmeter (120 VAC)
11.If desired, verify with a voltmeter (Figure17) that 120 VAC is present at the GFCI duplex receptacle and the 120V
Figure 17. 120 VAC GFCI Receptacle
5.Place the engine ON/OFF switch (Figure 20) in the "OFF" position. This step applies to units with S/N 5497957 and above.
Figure 20. Engine ON/OFF Switch (OFF)
6.Place the engine fuel valve lever (Figure 21) to the "OFF" position.”
Connecting the Load
1.Connect the load to the output receptacles.
2.Place the main circuit breaker (Figure 18) in the ON position.
Figure 21. Engine Fuel Valve Lever (OFF Position)
Emergency Showdown
1.Place the operation switch or engine ON/OFF swith (Figures19 or 20) in the "OFF" position.
Figure 18. Main Circuit Breaker (ON)
PAGE 26 — STOW