GANGING AND DERATING LIGHTING CONTROLS
Commercial Grade Lighting Controls
Ganging and Derating Box-Mounted Lighting Controls
Ganging is an installation practice where two or more lighting controls are mounted
Ganging and Derating Leviton Lighting Controls
When ganging Mural, True Touch, TouchPoint, ToggleTouch and IllumaTech controls, the side sections of the mounting strap must be removed. Use pliers to carefully bend side sections back and forth until they break off. The side sections of the strap dissipate heat, so removing them requires derating the dimmer’s capacity. See Chart 1.
Note that Leviton SureSlide and Trimatron lighting controls can be ganged without removing any sections of their mounting straps. However, SureSlide and Trimatron controls must also be derated when they’re ganged.
Maximum Load Per Dimmer for
Chart 1
Dimmer | Single |
| More Than |
Rating |
|
| |
500W | 500W | 400W | 300W |
|
|
|
|
600W | 600W | 500W | 400W |
1000W | 1000W | 800W | 700W |
|
|
|
|
400VA | 400VA | 350VA | 250VA |
600VA* | 600VA | 500VA | 400VA |
|
|
|
|
1000VA | 1000VA | 800VA | 700VA |
|
|
|
|
*Except
Maximum Bulb Wattage for Magnetic Low-Voltage Lighting
The capacity of a magnetic
Chart 2
Power To | Transformer | Lamp Load |
Transformer | Efficiency |
|
1000VA | X 80% | = 800W |
|
|
|
600VA | X 75% | = 450W |
|
|
|
Architectural
Ganging and Leviton Renoir® and Van Gogh® Architectural Lighting Controls
When fins are broken off on wide and narrow controls for ganging purposes, the number of switch boxes required can be quickly determined by referring to the two charts below.
Ganging
Specification
Switch boxes required |
|
|
|
| Number of Narrow Controls* | ||||
for ganging Leviton |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Controls |
| 0 | 0 |
| 1 | 2 | 3 | 4 | |
architectural controls |
|
| |||||||
when no fins are removed: |
|
|
|
|
|
|
|
|
|
|
| 0 | • |
| • | • | • | • | |
|
|
|
| ||||||
| Wideof |
|
|
|
|
|
|
| |
| 2 | 4 |
| 6 | 7 | 9 | 11 | ||
|
|
| 1 | 1 |
| 3 | 5 | 7 | 8 |
| Number |
|
|
|
|
|
|
| |
| 3 | 7 |
| 9 | 10 | 11 | 13 | ||
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 4 | 9 |
| 11 | 12 | 14 | 16 |
|
|
|
|
|
|
|
|
|
|
*Narrow controls must have fins broken off to be ganged.
Switch boxes required |
|
| Number of Narrow Controls |
|
| |||||||
for ganging Leviton |
|
|
|
|
|
|
|
|
|
| ||
| 0 |
|
|
|
|
|
|
|
| |||
0 | 1 | 2 | 3 | 4 |
| 5 | 6 | |||||
architectural controls |
|
| ||||||||||
when all inside fins |
|
|
|
|
|
|
|
|
|
|
| |
| 0 | 0 | 1 | 2 | 3 | 4 |
| 5 | 6 | |||
are removed: | Controls |
|
| |||||||||
|
|
|
|
|
|
|
|
|
| |||
| 1 | 1 | 3 | 4 | 5 | 6 |
| 7 | 8 | |||
|
|
| ||||||||||
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Wide |
| 2 | 3 | 5 | 6 | 7 | 8 |
| 9 | 10 | |
|
|
|
|
|
|
|
|
|
|
| ||
|
| 3 | 5 | 7 | 8 | 9 | 10 |
| 11 | 12 | ||
| of |
|
|
|
|
|
|
|
|
|
| |
|
| 4 | 7 | 9 | 10 | 11 | 12 |
| 13 | 14 | ||
| Number |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| ||
|
| 5 | 9 | 11 | 12 | 13 | 14 |
| 15 | 16 | ||
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 6 | 11 | 13 | 14 | 15 | 16 |
| 17 | 18 |
|
|
|
|
|
|
|
|
|
|
|
|
|