System Sensor B501BHT Wiring diagram, Detector Activates Sounder Bases - Complies with UL268

Models: B501BHT

1 4
Download 4 pages 18.46 Kb
Page 3
Image 3
Figure 4. Wiring diagram:

Figure 4. Wiring diagram:

Detector Activates Sounder Base(s) - (Complies with UL268)

UL has approved grouping for up to six B501BHT base with horn units. When wired as a group, any detector in the group that has its LED’s latched on by the panel will cause other B501BHT units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices to-

gether using terminal 5, Sounder Base Interconnect, as shown in the diagram.

NOTE: Since a local grouping of horns is not supervised, the groups can only be used as a supplementary evacuation system. It is not acceptable to group horns for primary alarm signaling.

LISTED COMPATIBLE

CONTROL PANEL

U.L.

 

 

 

 

 

 

CLASS A OPTIONAL WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INTELLIGENT

 

 

 

 

 

 

 

 

 

MONITOR

 

 

 

OPTIONAL SOUNDER INTERCONNECT*

 

 

 

MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

2

 

(+) COMM.

 

 

 

 

 

 

 

(–)

1 6

7

 

 

 

 

 

 

 

 

4

5

 

4

5

 

4

5

 

 

U.L.

 

3

2 1

 

3

2 1

 

3

2 1

LISTED

 

 

 

 

EOL

 

 

 

 

 

 

 

 

 

 

(–) COMM.

 

 

 

 

 

 

 

 

RESISTOR

 

 

 

 

 

 

 

 

 

 

47K

U.L.

LISTED

EOL

RELAY

(–) POWER

24V

EXTERNAL 24V SUPPLY

(+) POWER

CLASS A OPTIONAL WIRING

C0474-00

*GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.

Figure 5. Wiring diagram:

Detector Activates Sounder Base(s); Intelligent Relay Module Ac- tivates All Sounder Bases - (Complies with UL 268 and UL 464)

UL has approved grouping of up to six B501BHT bases with horn units. When wired as a group, any detector in the group that has its LED’s latched on by the panel will cause other B501BHT units in the group to sound. This type of “local”

grouping is accomplished by wiring the grouped devices to- gether using terminal 5, Sounder Base Interconnect, as shown in the diagram.

NOTE: Since a local grouping of horns is not supervised, the groups can only be used as a supplementary evacuation sys- tem. It is not acceptable to group horns for primary alarm signaling.

 

 

 

 

 

 

INTELLIGENT

 

 

 

 

 

OPTIONAL SOUNDER INTERCONNECT*

MONITOR

 

 

 

 

 

MODULE

UL LISTED

 

INTELLIGENT

 

 

 

 

COMPATIBLE

 

 

 

 

(+)

CONTROL

 

RELAY

FIRST

LAST

 

MODULE

(–)

PANEL

 

 

SOUNDER

SOUNDER

 

(+) COMM.

 

 

BASE

BASE

UL LISTED

SLC

 

 

 

 

(–) COMM.

 

 

 

 

EOL

 

 

 

 

 

 

RESISTOR

 

 

 

 

 

 

47k

 

 

 

 

 

 

UL

 

 

 

 

 

 

LISTED

 

 

 

 

 

 

EOL

 

(–) POWER

 

 

 

 

RELAY

UL LISTED

 

 

 

 

24V

 

 

 

 

 

 

24V SUPPLY

(+) POWER

 

 

 

 

 

 

THIS IS A STANDARD RELAY

 

 

 

 

 

MODULE CONFIGURED TO

 

 

 

 

 

 

REVERSE THE POWER

 

 

 

C0968-00

 

 

 

 

 

 

*GROUPING OF UP TO 6 MODEL B501BHT TEMPORAL TONE SOUNDER BASES.

D550-06-00

3

I56-1367-004R

Page 3
Image 3