INSTALLATION AND MAINTENANCE INSTRUCTIONS

 

 

 

 

 

 

3825 Ohio Avenue, St. Charles, Illinois 60174

EM-1RI Relay Module

 

 

 

 

1-800-SENSOR2, FAX: 630-377-6495

 

 

 

 

www.systemsensor.com

 

 

 

 

 

 

 

 

 

SPECIFICATIONS

 

 

 

 

 

 

 

Normal Operating Voltage:

 

15 to 30 VDC

 

 

 

 

Standby Current:

 

500 µA max. average (continuous broadcasts)

 

 

 

Alarm Current:

 

2.0 mA (red LED on)

 

 

 

 

Short Circuit Current

 

 

 

 

 

 

 

Dry Control Input:

 

30 µA max. Avg. (5VDC)

 

 

 

 

Maximum Resistance

 

 

 

 

 

 

 

Dry Contact Input:

 

100 Ω

 

 

 

 

Temperature Range:

 

32°F to 120°F (0°C to 49°C)

 

 

 

Humidity:

 

10 to 93% RH Non-condensing

 

 

 

Dimensions:

 

4.17˝ H x 4.26˝ W x 1.22˝ D

 

 

 

 

 

 

(106 mm H x 108 mm W x 31 mm D)

 

 

 

Accessories:

 

Wall cover plate (included)

 

 

 

 

 

 

SMB500 Surface Mount Electrical Box

 

 

 

 

 

 

CB500 Control Module Barrier

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CURRENT RATING

MAXIMUM VOLTAGE

 

LOAD DESCRIPTION

 

APPLICATION

 

 

3 A

 

30 VDC

 

Resistive

 

Non-Coded

 

 

2 A

 

30 VDC

 

Resistive

 

Coded

 

 

.9 A

 

110 VDC

 

Resistive

 

Non-Coded

 

 

.9 A

 

125 VDC

 

Resistive

 

Non-Coded

 

 

.5 A

 

30 VDC

 

Inductive (L/R=5ms)

 

Coded

 

 

1 A

 

30 VDC

 

Inductive (L/R=2ms)

 

Coded

 

 

.3 A

 

125 VAC

 

Inductive (PF=.35)

 

Non-Coded

 

 

1.5 A

 

25 VAC

 

Inductive (PF = .35)

 

Non-Coded

 

 

.7 A

 

70.7 VAC

 

Inductive (PF=.35)

 

Non-Coded

 

 

2 A

 

25 VAC

 

Inductive (PF=.35)

 

Non-Coded

 

NOTE: This module is not approved for use in the European Union, at or above 50VAC or 70VDC.

I56-2023-004

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to the appropriate control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service.

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

Relay Module, Model EM-1RI, is to be designed for use in activa- tion of the types of products that are generally connected to an in- telligent fire alarm system. It provides two sets of form C contacts that switch together (one DPDT relay). There is also an input that is capable of monitoring a dry set of contacts for open or closed conditions. The module also has on-board short circuit isolators to prevent shorts on the signaling line circuit from disabling more than one device on the intelligent loop.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a listed compatible control panel.

MOUNTING

The module mounts directly to 4˝ square electrical boxes. The box must have a minimum depth of 218˝. Modules must be mounted with the arrow facing upward for proper operation of the IR pro- gramming tool. Surface mounted electrical boxes (SMB500) are available from System Sensor.

LED

INDICATOR

IR

RECEIVER

C0166-00

D500-61-00

1

I56-2023-004

Page 1
Image 1
System Sensor EM-1RI specifications Installation and Maintenance Instructions, Specifications, Before Installing, Mounting