INSTALLATION AND MAINTENANCE INSTRUCTIONS
|
|
|
|
|
| 3825 Ohio Avenue, St. Charles, Illinois 60174 | ||
|
|
|
|
| ||||
|
|
|
| www.systemsensor.com | ||||
|
|
|
|
|
|
|
|
|
SPECIFICATIONS |
|
|
|
|
|
|
| |
Normal Operating Voltage: |
| 15 to 30 VDC |
|
|
|
| ||
Standby Current: |
| 500 µA max. average (continuous broadcasts) |
|
|
| |||
Alarm Current: |
| 2.0 mA (red LED on) |
|
|
|
| ||
Short Circuit Current |
|
|
|
|
|
|
| |
Dry Control Input: |
| 30 µA max. Avg. (5VDC) |
|
|
|
| ||
Maximum Resistance |
|
|
|
|
|
|
| |
Dry Contact Input: |
| 100 Ω |
|
|
|
| ||
Temperature Range: |
| 32°F to 120°F (0°C to 49°C) |
|
|
| |||
Humidity: |
| 10 to 93% RH |
|
|
| |||
Dimensions: |
| 4.17˝ H x 4.26˝ W x 1.22˝ D |
|
|
| |||
|
|
| (106 mm H x 108 mm W x 31 mm D) |
|
|
| ||
Accessories: |
| Wall cover plate (included) |
|
|
| |||
|
|
| SMB500 Surface Mount Electrical Box |
|
|
| ||
|
|
| CB500 Control Module Barrier |
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
| CURRENT RATING | MAXIMUM VOLTAGE |
| LOAD DESCRIPTION |
| APPLICATION |
| |
| 3 A |
| 30 VDC |
| Resistive |
|
| |
| 2 A |
| 30 VDC |
| Resistive |
| Coded |
|
| .9 A |
| 110 VDC |
| Resistive |
|
| |
| .9 A |
| 125 VDC |
| Resistive |
|
| |
| .5 A |
| 30 VDC |
| Inductive (L/R=5ms) |
| Coded |
|
| 1 A |
| 30 VDC |
| Inductive (L/R=2ms) |
| Coded |
|
| .3 A |
| 125 VAC |
| Inductive (PF=.35) |
|
| |
| 1.5 A |
| 25 VAC |
| Inductive (PF = .35) |
|
| |
| .7 A |
| 70.7 VAC |
| Inductive (PF=.35) |
|
| |
| 2 A |
| 25 VAC |
| Inductive (PF=.35) |
|
|
NOTE: This module is not approved for use in the European Union, at or above 50VAC or 70VDC.
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the appropriate control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
Relay Module, Model
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a listed compatible control panel.
MOUNTING
The module mounts directly to 4˝ square electrical boxes. The box must have a minimum depth of 21⁄8˝. Modules must be mounted with the arrow facing upward for proper operation of the IR pro- gramming tool. Surface mounted electrical boxes (SMB500) are available from System Sensor.
LED
INDICATOR
IR
RECEIVER
1 |