WIRING

NOTE: All wiring must conform to applicable local codes, ordi- nances, and regulations.

1.Install module wiring in accordance with the job drawings and appropriate wiring diagrams.

NOTE: Separate cable entry openings must be used to maintain required spacing between power limited and non-power lim- ited wiring. Optional EA-CB may be required to separate power limited and non power limited wiring in the electrical box.

2.Set the address on the module per job drawings using the IR configuration tool (model no. EA-CT).

3.Secure module to electrical box (supplied by installer).

AUTO ADDRESSING

Eclipse Series devices are capable of supporting auto addressing, if the fire alarm control panel is designed to do so. In auto ad- dressing, the control panel, through the use of each device’s on- board isolators, can automatically assign device addresses.

In order to control which devices are addressed first in wiring configurations with branches, a branch marker can be set at a particular device. A branch marker is an electronic value from 0 to 255 stored in the device memory. The branch markers are set with the IR configuration tool, EA-CT.

TERMINAL DEFINITIONS

T1

(+) SLC in/out

T7

Normally Closed #1

T2

(–) SLC in/out

T8

Common #1

T3

(+) SLC in/out

T9

Normally Open #1

T4

(–) SLC in/out

T10

Normally Closed #2

T5

(+) Dry Contact Input

T11

Common #2

T6

(–) Dry Contact Input

T12

Normally Open #2

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state dur- ing shipping. To ensure that the switch contacts are in their cor- rect state, modules must be made to communicate with the panel before connecting circuits controlled by the module.

Figure 2: Wiring Diagram

RELAY {

CONTACTS

SIGNAL LINE CIRCUIT (SLC)

IS SUPERVISED AND

POWER LIMITED

12

1

(+)

)–(

11

2

(+)

10

3

)–(

9

4

 

85

76

SIGNAL LINE CIRCUIT (SLC)

30 VDC MAX.

TWISTED PAIR RECOMMENDED

(+)

 

)–(

FROM PANEL OR

PREVIOUS PANEL

 

(+)

 

)–(

TO NEXT DEVICE

CONNECT MODULES

TO LISTED COMPATIBLE CONTROL PANELS ONLY

NORMALLY OPEN (T12)

 

 

 

 

 

 

 

 

 

 

 

 

COMMON (T11)

 

 

 

 

RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTACT #2

 

NORMALLY CLOSED (T10)

 

 

 

 

 

 

MODULE DOES NOT SUPERVISE

 

 

 

 

 

 

CONTROLLED CIRCUITS.

 

 

 

 

 

 

TERMINALS 1-6 ARE POWER LIMITED.

 

 

 

 

 

 

TERMINALS 7-12 ARE NON-POWER LIMITED.

 

 

 

 

 

 

NORMALLY OPEN (T9)

 

 

 

 

 

C0110-02

 

 

 

 

 

COMMON (T8)

 

 

 

 

RELAY

 

 

 

 

 

 

 

 

 

 

NORMALLY CLOSED (T7)

 

 

 

 

CONTACT #1

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: NORMALLY OPEN

 

 

 

 

 

 

OR NORMALLY CLOSED

Three-Year Limited Warranty

System Sensor warrants its enclosed module to be free from defects in materi- als and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this module. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the module which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please

include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or altera- tions occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to pro- vide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

Reorient or relocate the receiving antenna.

Increase the separation between the equipment and receiver.

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

Consult the dealer or an experienced radio/TV technician for help.

D500-61-00