Optional Modules 2. Installation
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 27
LED Interface Module - 4XLM
Connect the terminals on TB1 of the LED Interface Module to the corresponding terminals of the RZA-
4X Remote Annunciator.
Make wiring connections with system power off.
Maximum wire impedance is 50 ohm per wirin g connection.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring
Requirements" on page 17.
Figure 18 Connection of 4XLM to RZA-4X
SYSTEM TROUBLE
RE-SOUND
TONE
SILENCE
FIRE ALARM ANNUNCIATOR
TB1
J2
Connect to corresponding
terminals of the RZA-4X
Remote Annunciator.
Front View Side View
MS44--4xlmfconn.cdr
Single-gang
Box
+24V
Out #1
Out #2
Out #3
Out #4
Sysyem Trouble
Sound
Resound